Build Equinox CERV-001-PARTA Installation Manuals Download Page 8

 

Revision 0.36 [01/27/2015] 

Page 8 

 

W

ATER 

D

RAIN

 

1.

 

Prime the outside of the PVC drain tube, and then connect your drain to the fitting 
with PVC cement. 

2.

 

It is imperative to create a water trap

 in the drain tube.  If you do not, you will most 

likely hear a gurgling sound as the system runs and water will not drain properly.  A 
small loop or jog in the drain tubing (as seen below) is often enough. 

 

3.

 

If the drain is below the CERV and condensate is removed by gravity, the tubing may 
simply be run to the drain.  If the drain is higher (for instance, a wall drain), you must 
use a condensate pump to actively remove the drained condensate. 

4.

 

If you have an overflow water pan underneath the CERV, such as a washing machine 
pan, cut a hole in it and attach a fitting and drain tube to the floor drain/condensate 
pump. 

 

E

LECTRICAL

 

1.

 

For further electrical information, see the Appendix at the end of the document. 

2.

 

MAKE SURE THE CIRCUIT IS NOT HOT, i.e. breaker switch is off or fuse is out.   

3.

 

Run electrical supply (240vAC) to the CERV-001-PARTA module.  The power input from 
your supply panel connects to the 16 gauge Red and Black wires in the junction box on 
the module.  Ground the power input with the included green ground screw. 

4.

 

Run electrical supply (120vAC) to the CERV-001-PARTB module.  The power input from 
your supply panel connects to the 16 gauge White and Black wires labeled 120vN and 
120vH in the high voltage junction box on the module.  Ground the power input with 
the included green ground screw. 

Summary of Contents for CERV-001-PARTA

Page 1: ...INSTALLATION MANUAL CONDITIONING ENERGY RECOVERY VENTILATOR CERV MODEL CERV 001 PARTA CERV 001 PARTB REV 0 36 01 27 2015...

Page 2: ...Revision 0 36 01 27 2015 Page 2 CERV SYSTEM FOOTPRINT NAMEPLATE RATINGS...

Page 3: ...pump must be used 5 An inline water trap must be effectively utilized as detailed later to prevent air from being drawn into the CERV 001 PARTA unit through the drain tubing INSTALLATION PROCEDURE 1...

Page 4: ...the PARTA and PARTB units together rigid galvanized duct fittings should be used All ducting between the units must be insulated and sealed especially the outlet side since the air will be heated or...

Page 5: ...nature of the system there are several ways to duct the CERV for operation See the following to determine the most applicable configuration DUCTING WITH AN EXISTING MINISPLIT FURNACE CABINET DUCTING W...

Page 6: ...dditionally you may wish to filter the return air to remove dust or other particulates from the air when the CERV is in a recirculation mode The filter boxes that are typically supplied with the CERV...

Page 7: ...ound at home improvement stores In colder climates it may be necessary to add additional insulation if it appears that the ducts may be showing signs of sweating FILTER BOXES The Fantech FB6 filter bo...

Page 8: ...erflow water pan underneath the CERV such as a washing machine pan cut a hole in it and attach a fitting and drain tube to the floor drain condensate pump ELECTRICAL 1 For further electrical informati...

Page 9: ...hite wire in the HV junction box The supply blower wires will be labeled BinN and BinH while the exhaust blower wires will be labeled BoutN and BoutH Blowers may share the same ground green 6 Run the...

Page 10: ...luded with the heater This wire will only carry a low current 24vAC control signal therefore thermostat wire may be acceptable if the included wire is not long enough b Set the Warm Air dial pictured...

Page 11: ...labels b Wires may be run through the same stress relief as the PARTA wiring and the wireless relay can be secured with a strip of Velcro not included c A short length of adhesive backed Hook and Loop...

Page 12: ...001 PARTA CERV 001 PARTB Volts AC 240 Volts AC 120 Amps 2 1 Amps 2 5 Ph 1 Ph 1 Hz 60 Hz 60 Minimum Circuit Ampacity 8 75 Minimum Circuit Ampacity 2 5 Max Fuse Size Amps 15 Max Fuse Size Amps 15 Blowe...

Page 13: ...TRAL wire white Bin H Red Connect to INDOOR SUPPLY BLOWER HOT wire black Bin N white Connect to INDOOR SUPPLY BLOWER NEUTRAL wire white Bout H Red Connect to OUTDOOR EXHAUST BLOWER HOT wire black Bout...

Reviews: