Thermotronik TT-77

9.7 Menu Sequence Overview

Configuration

Equipment configuration

t___

____

Display

Measurement display

Main menu

Submenu 1

Submenu 2

Submenu 3

Sets a value for frequency 100 Hz (only OUT1 and OUT2)

Settings and Display Menu

SP1
FI.Hi

____

____

Temperature

Temperature main menu

tEMP

____

Out 1
Settings menu OUT1

out1

____

SP1

Switching point 1

____

____

Selection menu

0°C - 100°C

____

____

Switch-back point 1

____

____

Selection menu

____

Amount of time the signal must be present for output OUT1 to trigger.
Setting range: 0...100 seconds (for frequency output without function)

____

EF 1
Extended functions

EF1

____

Delay SP 1

Delay OUT1 On

dS1

____

Selection menu

0 - 100

___

Amount of time the signal must be present for output OUT1 to switch back.
Setting range: 0...100 seconds (for frequency output without function)

____

Delay RP 1

Delay OUT1 Off

dr1

____

Selection menu

___

Frequency output 1-100 Hz

____

Set Out 1

Definition OUT1

ou1

____

Selection menu

Hno - FM

___

Definition of switching characteristics for output 1:

FM

____

Check Out 1

Functional test OUT1

C.ou1

____

Selection menu

n.op - on

____

Normal switching output operation
Switching output Off /
Switching output On /

n.oP
oFF
on

F1
F100

Simulation 1 Hz
Simulation 100 Hz

____

Exit

Exit menu level

E

____

LED Out 1

Function status LED1

LEd1

____

Selection menu

L= o - L=-o

L=__

FH1

Define maximum window limit

Setting the switching point /

Sets a value for frequency 1 Hz (only OUT1 and OUT2)

rP1
FI.Lo

FL1

Set lower window limit

Set switch-back point /

Hno Hnc

Hysteresis function NO contact or NC contact

Fno Fnc

Window function NO contact or NC contact /

LED = -output: inverted to switching output

L= o
L=-o

LED = output: follows switching output

0°C - 100°C

0 - 100

FH1   F1.Hi

rP1

FL1   F1.Lo

____

Exit
Exit menu level

E

or 60s no action:

Exit main/submenu

Shortcut

+

See menu structure Out1

Not applicable for version with 

analogue output

____

Out x

Settings menu OUTx

out_

____

Analog Max1

Set maximum value

A1.Hi

____

Selection menu

0°C - 100°C

____

Sets the maximum analogue output signal to a defined value.
(Note: Max. – Min >= 10 % of the measuring range)

____

Analog Min1

Set minimum value

A1.Lo

____

Selection menu

0°C - 100°C

____

i I

____

Set A.Out1

Output function

A.ou1

____

Selection menu

i 1 - u 3

_ _

u 1

4...20 mA

Selecting the analogue output function:

Output mean analogue value  /

n.oP
HALF

____

Check An1

Functional test Analog 1

C.An1

____

Selection menu

n.oP - Lo

____

Hi

Output maximum analogue value

Analogue output normal mode /

____

Analog Out1

Settings menu Analog 1

An1

____

Exit

Exit menu level

E

Exit menu level

E

Exit

Sets the maximum analogue output signal to a defined value.
(Note: Max. – Min >= 10 % of the measuring range)

2...10 V

u 2

0...10 V

u 3

0...5 V

Lo

Minimum analogue value output

Alternate menu for version with analogue output

Not applicable when ordered with 2 or more 

switching outputs

b.EF

Basic Adv. Functions

Basic EF

Factory setting

rES

Reset

____

Confirm

no - YES

___

Resets the device to delivery status

Temperature unit

t.uni

Set Unit Temp

____

Selection menu

°C - °F

°_

°C

[Celsius],

Selecting the temperature unit displayed:

Display rate

di5

Display Rate

____

Selection menu

FASt - off

____

Keylock

Loc

Lock Device

____

Selection menu

0 - 999

___

Exit menu level

E

Exit

°F

[Fahrenheit]

Selecting the display refresh rate:

FASt

[fast],

Medi

[medium],

SLo

[slow],

Activating the keylock by entering a numerical code >

0

Master code

287

oFF

[Display off]

diA

Diagnostics menu

Diagnostic

Log output

J.out

Journal Out

____

Jor I - ---

____

Displays the last 6 delete function.

Max/Min memory

t.MM

Max/Min Temp

____

Selection menu

____ - ---

Output monitoring

SJ.ou

Set Journal Out

____

Selection menu

Out1 - Out_

out_

Selecting the alarm output to be logged

Min/Max Delay

dt.MM

Delay MM

____

Selection menu

0 - 100

___

Amount of time the signal must be present before saving the maximum / minimum value.
Setting range: 0...100 seconds

Displays delete function.

Selection menu

Display:

X – amount of time passed in hours/days; scroll through journal with ▲▼

JorX

Display: Value – amount of time passed in hours/days; scroll through journal with ▲▼

____

Exit menu level

E

Exit

E

Exit menu level

Exit

Pt100 lead length

t.CL

Cable Length

____

Selection menu

0M - 20m

__M

Pt100 cable cross-section

t.CS

Cable Cross

____

Selection menu

0.25( - 1.5(

_.__(

Alternate menu 

for version with wall mount

Not used when ordered with attached 

detector

Pt100 line length in metres (supply line length x number of conductors), for compensating
the supply line resistance.   ΔT [Δ°C] = 0.462 [Δ°C] x length [m] / cross-section [mm²]

Pt100 line cross-section in millimetres  , for compensating the supply line resistance

2

Error handling

Err.h

Set error handling

____

Selection menu

;no - YES

___

Disable/enable normal error handling and analysis

Set Out 1

r.ou 1

reassign O1

____

Selection menu

tEMP - Err

____

Set switching output Out 1 to function or to error signal

Set Out 2

r.ou 2

reassign O2

____

Selection menu

tEMP -Err

____

Set switching output Out 2 to function or to error signal

34

Bühler Technologies GmbH

BE140013 ◦ 07/2019

Summary of Contents for Thermotronik TT-77

Page 1: ...instructions Display and control unit Thermotronik TT 77 BE140013 07 2019 B hler Technologies GmbH Harkortstr 29 D 40880 Ratingen Tel 49 0 21 02 49 89 0 Fax 49 0 21 02 49 89 20 E Mail fluidcontrol bu...

Page 2: ...ad this instruction carefully prior to installation and or use Pay at tention particularly to all advises and safety instructions to prevent in juries B hler Technologies can not be held responsible f...

Page 3: ...of the switching characteristic 16 5 7 2 Switching output x Upper switching limit switching point 17 5 7 3 Switching output x Lower switching limit switch back point 18 5 7 4 Switching output x Switc...

Page 4: ...T 77 9 4 Standard pin assignment TT 77W 32 9 5 Current settings 33 9 6 Display ranges 33 9 7 Menu Sequence Overview 34 9 8 Display resolution 35 10 Attached documents 36 ii B hler Technologies GmbH BE...

Page 5: ...on the configuration The outputs are freely programmable The available versions are TT77F The display and control unit can be mounted to the tank along with the switching tube TT77W The display and c...

Page 6: ...s 2 x PNP output 2T K 2T 4 x PNP output 4T 1 x PNP output 1 x analogue output 1T K 2 x PNP output 1 x analogue output 4T K 4 x PNP output 1 x analogue output TT 77F tank mounted version 1 x IO Link 1...

Page 7: ...This manual is part of the equipment The manufacturer keeps the right to modify specifications without advanced notice Keep this manual for later use Signal words for warnings DANGER Signal word for...

Page 8: ...ons are observed during disposal compliance with national installation regulations Maintenance Repair Please note during maintenance and repairs Repairs to the unit must be performed by B hler authori...

Page 9: ...rt the product inside the original packaging or a suitable alternative The equipment must be protected from moisture and heat when not in use It must be stored in a covered dry dust free room at room...

Page 10: ...into the designated bore on the tank When installed with remote display the display and control unit are mounted to a 35 mm 1 4 top hat rail The sensor connects with a line The connector for the sens...

Page 11: ...r message appears in the display during operation please refer to the Troubleshooting table under chapter Service and Repair 5 2 LED statuses LEDs above the measurement display indicate the status of...

Page 12: ...select a menu item and to enter values Open the main menu with the key Select the submenu with the and keys and open the submenu with the key If necessary select the next submenu with the and keys and...

Page 13: ...Out 1 out_ Settings menu OUTX Out X An 1 Settings menu Analog 1 Analog Out 1 E Exit menu level Exit b EF Basic Adv Functions Basic EF If applicable If applicable DiA Diagnostics menu Diagnostic E Exi...

Page 14: ...handling and analysis The function Disable error handling Err h is used to disable normal error handling and analysis This may pose dangers to the user or machine Basic EF b EF Basic ext functions Er...

Page 15: ...1 5 Selection menu Setting range 0 25 to 1 5 Measuring cable cross section for compensating the Pt100 supply line resistance 5 6 5 Define switching outputs Here you can define the switching outputs U...

Page 16: ...fter entering at least one digit 0 A dot indicates the active digit during this input Setting range 000 to 999 Use the key to open the list of values Enter the digit using the and keys 0 to 9 and pres...

Page 17: ...pecific specifications the factory preset may vary from those listed here Basic settings Basic Settings t uni C dis FASt Loc 000 tcl 0 0m tcC 0 50II for wall mounting only Version with 1 switching out...

Page 18: ...ions are Hysteresis Function Hysteresis function as the NO contact Hysteresis function as the NC contact NO contact or NC contact function when the output signal is set when exceeding the configured s...

Page 19: ...nc Note The designation of the switching function may vary Measured variable 5 7 2 Switching output x Upper switching limit switching point The upper switching limit for switching output Out x can be...

Page 20: ...easured variable ____ out_ Measured variable main menu Out X EF_ EF X Advanced Functions dS_ Delay SP X Delay OUTX On ___ Selection menu 0 100 Settings menu OUTX Setting range 0 100 seconds Time span...

Page 21: ...2 switching outputs Assignment for 4 switching outputs 1 LED 1 yellow LED 1 yellow LED 1 yellow 2 LED 2 red LED 2 red 3 LED 3 yellow 4 LED 4 red In the factory setting the LED indicates the physical s...

Page 22: ...status LEDX L __ Selection menu L o L _o Settings menu OUTX The options are LED output the LED lights up when the PNP switching output is closed LED output the LED lights up when the PNP switching ou...

Page 23: ...output with different value ranges This is configured in menu Measured variable ____ An_ Measured variable main menu Analog OutX A ou_ Set A OUtX Output function _ _ Selection menu i I u 3 Settings me...

Page 24: ...last 6 events for the switching output being logged can be viewed here and all entries deleted Diagnostic diA Diagnostics menu J out Log output Journal Out ____ Jor I Selection menu The journal entrie...

Page 25: ...ing output to be logged Only one switching output can be logged Diagnostic diA Diagnostics menu SJ ou Output monitoring Set Journal Out out_ Out I Out_ Selection menu Options out1 to outx Switching ou...

Page 26: ...tenance This device is maintenance free The method for cleaning the devices must be adapted to the IP protection class of the devices Do not use cleaners which could damage the device materials 24 B h...

Page 27: ...eted and signed RMA decontamination statement to the packaging We will otherwise be unable to process your repair order You will find the form in the appendix of these instructions or simply request i...

Page 28: ...orrect output current Wrong signal type set In submenu Aoux Check and if necessary set the correct signal type current voltage out put Load too high current output Reduce load to permissible value Ana...

Page 29: ...sposal Dispose of parts so as not to endanger the health or environment Follow the laws in the country of use for disposing of elec tronic components and devices during disposal 27 B hler Technologies...

Page 30: ...s Current input during operation approx 50 mA without current and switching outputs Supply voltage UB 10 30 V DC nominal voltage 24 V DC with IO Link 18 30 V DC Ambient temperature 20 C to 70 C Displa...

Page 31: ...with 1 x assignable to alarm logbook with 1 x assignable to alarm logbook max switching current 0 5 A per output continuous short circuit protected Output 1 max 0 2 A Contact load max 1 A total Analo...

Page 32: ...r 100 ms Current input during operation approx 50 mA without current and switching outputs Supply voltage UB 10 30 V DC nominal voltage 24 V DC with IO Link 18 30 V DC Ambient temperature 20 C to 70 C...

Page 33: ...4 20 mA 2 10 V DC 0 10 V DC 0 5 V DC Max load as current output UB 8 V 0 02 A UB 8 V 0 02 A UB 8 V 0 02 A Min input load as voltage output 10 k 10 k 10 k also programmable as frequency output Output 1...

Page 34: ...connection Version 1D1S 2T 1T KT 2T KT 4T 4T KT M12 base 4 pin 4 pin 4 pin 5 pin 8 pin 8 pin Panel plug Pin 1 2 3 4 5 6 7 24 V DC T2 PNP GND C Q IO Link 24 V DC T2 PNP GND T1 PNP 24 V DC Analogue GND...

Page 35: ...4 rP4 r ou3 ds4 dr4 ou4 r ou4 Di5 Loc Analogue outputs tcl A1 Hi A1 Lo A ou1 tcC A2Hi A2 Lo A ou2 for wall mounting only Date Signature 9 6 Display ranges Name Menu Unit Display Range from with unit R...

Page 36: ...ction menu n oP Lo ____ Hi Output maximum analogue value Analogue output normal mode ____ Analog Out1 Settings menu Analog 1 An1 ____ Exit Exit menu level E Exit menu level E Exit Sets the maximum ana...

Page 37: ...100 x 200 0 5 100 x 200 0 5 200 x 500 1 200 x 500 1 500 x 1000 2 500 x 1000 2 1000 x 5 1000 x 5 none non2 2 fixed point numbers Range x Resolution x 5 0 01 5 x 10 0 02 10 x 20 0 05 20 x 50 0 1 50 x 1...

Page 38: ...Thermotronik TT 77 10 Attached documents Declaration of conformity KX110020 Decontamination statement 36 B hler Technologies GmbH BE140013 07 2019...

Page 39: ......

Page 40: ...aminated Ja kontaminiert mit Yes contaminated with explosiv explosive entz ndlich flammable brandf rdernd oxidizing komprimierte Gase compressed gases tzend caustic giftig Lebensgefahr poisonous risk...

Page 41: ...rsetzen Sie vor der Inbetrieb nahme die Verkabelung wieder in den urspr nglichen Zustand Fragen Sie im Zweifel beim Hersteller nach weiteren Informationen Analysing defective assemblies is an essentia...

Reviews: