Fluidcontrol

Installation and Operation Instructions

Original instructions

Temperature sensor

TF with IO-Link

BE140016
09/2020

Bühler Technologies GmbH, Harkortstr. 29, D-40880 Ratingen

Tel. +49 (0) 21 02 / 49 89-0, Fax: +49 (0) 21 02 / 49 89-20

E-Mail: [email protected]

Internet: www.buehler-technologies.com

Summary of Contents for TF with IO-Link

Page 1: ...iginal instructions Temperature sensor TF with IO Link BE140016 09 2020 Bühler Technologies GmbH Harkortstr 29 D 40880 Ratingen Tel 49 0 21 02 49 89 0 Fax 49 0 21 02 49 89 20 E Mail fluidcontrol buehler technologies com Internet www buehler technologies com ...

Page 2: ...ead this instruction carefully prior to installation and or use Pay at tention particularly to all advises and safety instructions to prevent in juries Bühler Technologies can not be held responsible for misusing the product or unreliable function due to unauthorised modifications All rights reserved Bühler Technologies GmbH 2020 Document information Document No BE140016 Version 09 2020 ...

Page 3: ...ral hazard warnings 4 3 Transport and storage 5 4 Installation and connection 6 4 1 Installation 6 4 2 Electrical Connections 6 5 Operation and control 7 6 Cleaning and Maintenance 8 7 Service and repair 9 7 1 Spare parts and accessories 9 8 Disposal 10 9 Appendix 11 9 1 Technical Data 11 9 2 Standard pin assignment 11 10 Attached documents 12 i Bühler Technologies GmbH BE140016 09 2020 ...

Page 4: ... the temperature sensors when establishing the connection 1 2 Layout and Functionality Type TF temperature sensors use a Pt100 temperature sensor to generate a temperature dependent resistance signal The Pt100 sensor is installed at the lowest point of the sensor tube to always ensure sufficient contact with the medium being measured The electronics of the TF temperature sensor converts this resis...

Page 5: ... This manual is part of the equipment The manufacturer keeps the right to modify specifications without advanced notice Keep this manual for later use Signal words for warnings DANGER Signal word for an imminent danger with high risk resulting in severe injuries or death if not avoided WARNING Signal word for a hazardous situation with medium risk possibly resulting in severe injuries or death if ...

Page 6: ...ned Safety guards are used and mandatory maintenance is performed Legal regulations are observed during disposal compliance with national installation regulations Maintenance Repair Please note during maintenance and repairs Repairs to the unit must be performed by Bühler authorised personnel Only perform conversion maintenance or installation work described in these operating and installation ins...

Page 7: ...t the product inside the original packaging or a suitable alternative The equipment must be protected from moisture and heat when not in use It must be stored in a covered dry dust free room at room temperature 5 Bühler Technologies GmbH BE140016 09 2020 ...

Page 8: ...s clean and even Only screw the temperature sensor into the designated thread Sealed with an elastic sealing ring No other sealants required 4 2 Electrical Connections Electricity is supplied via plug connectors Please refer to the appendix for installation dimensions nominal voltage and plug configuration The switching outputs are PNP transistors The level and temperature sensor is powered with 1...

Page 9: ...nfiguring the unit during operation The IODDs required to configure the unit is available at https ioddfinder io link com If the IO Link interface is not being used no master or only used to parametrise the temperature sensor functions as a regular temperature sensor with 2 switching outputs The default parameters and switching function of the switching outputs how ever can be parametrised via IO ...

Page 10: ...tenance This device is maintenance free The method for cleaning the devices must be adapted to the IP protection class of the devices Do not use cleaners which could damage the device materials 8 Bühler Technologies GmbH BE140016 09 2020 ...

Page 11: ... Bühler Technologies GmbH Reparatur Service Harkortstraße 29 40880 Ratingen Germany Please also attach the completed and signed RMA decontamination statement to the packaging We will otherwise be unable to process your repair order You will find the form in the appendix of these instructions or simply request it by e mail service buehler technologies com 7 1 Spare parts and accessories Accessories...

Page 12: ...sposal Dispose of parts so as not to endanger the health or environment Follow the laws in the country of use for disposing of elec tronic components and devices during disposal 10 Bühler Technologies GmbH BE140016 09 2020 ...

Page 13: ...ths 280 370 500 standard variable to max 1000 mm Input value Sensor element Pt100 Class B DIN EN 60751 Tolerance Pt100 0 8 C Operating voltage UB 18 30 VDC Measuring range 20 C to 120 C Output IO Link IO Link Revision 1 1 Baudrate COM3 230 4 k SIO Mode Yes Min Time Period 10 ms 9 2 Standard pin assignment Connector M12 Dimensions Number of pins 4 pin DIN EN 61076 2 101 IP rating IP67 with IP67 cab...

Page 14: ...TF with IO Link 10 Attached documents Declaration of Conformity KX110021 IO Link HX00002 manufacturer declaration RMA decontamination statement 12 Bühler Technologies GmbH BE140016 09 2020 ...

Page 15: ......

Page 16: ...r Clogging indicator BCI24 Dx 3x7 Geberrohr Transducer tube BLT AMx LD Temperaturfühler mit IO Link Temperature sensor with IO Link TF TT 77F folgenden Spezifikationen entsprechen meet the following specifications IO Link Interface and System Specification V1 1 July 2013 Note 1 2 IO Device Description V 1 1 August 2011 NOTE 1 Relevant Test specification is V1 1 July 2014 NOTE 2 Additional validity...

Page 17: ...aminated Ja kontaminiert mit Yes contaminated with explosiv explosive entzündlich flammable brandfördernd oxidizing komprimierte Gase compressed gases ätzend caustic giftig Lebensgefahr poisonous risk of death gesundheitsge fährdend harmful to health gesund heitsschädlich health hazard umweltge fährdend environmental hazard Bitte Sicherheitsdatenblatt beilegen Please enclose safety data sheet Das ...

Page 18: ...ersetzen Sie vor der Inbetrieb nahme die Verkabelung wieder in den ursprünglichen Zustand Fragen Sie im Zweifel beim Hersteller nach weiteren Informationen Analysing defective assemblies is an essential part of quality assurance at Bühler Technologies To ensure conclusive analysis the goods must be inspected unaltered if possible Modifications or other damages which may hide the cause or render it...