1
Deferred operation time of setting protection, unit(s).
5.9.3 Setting calculation of protection
Please see
Rules
and
Regulations
.
5.9.4 Sensitivity checking
Please see
Rules
and
Regulations
.
5.10 Reverse power protection of generator
5.10.1 Protection principle
Reverse power protection is used to protect steam turbine. When emergency stop valve is switched off
by accident or the unit protection operation closes emergency stop valve and exits breaker and does not trip,
generator will be operated as electromotor to absorb active power from the system. Tail blade of steamer
will probably overheat to cause destroy of steamer due to blast loss. Reverse power protection can have a
good protection role. Two sets of independent reverse power protections are equipped on large generating
unit.
Reverse power protection reaction generator absorbs active power from the system and reverse power
is blocked by TV breakage.
Voltage is from generator terminal TV and current is from generator neutral point (or generator
terminal) TA.
Tripping mode: signaling or tripping
5.10.2 Setting contents
1) Power element setting ID - P
1.dz
Size of setting reverse power, setting input, reverse power, unit (W).
2) Operation time t
1
Deferred operation time of setting protection, unit(s)
5.10.3 Setting calculation of protection
1) Power element setting ID - P
1.dz
It is set to ensure steamer safety and possible accidents in maximum reactive power of generator in
Signaling or tripping
P<-P
NG
.zd1
t1/0
Figure 5-14 Reverse power protection logic