2
Burner installation
24
Installation and maintenance instructions Logano GE315 • Issue 02/2006
We reserve the right to make any changes due to technical modifications.
2.6.6
Fit the flue gas pipe sealing collar
(optional accessory)
z
Insert the flue gas pipe until it contacts the flue gas
collector coupling.
z
Place the flue gas pipe sealing collar on the top so
that it overlaps the flue gas pipe and the coupling.
z
Place the jubilee clips (Fig. 29,
Item 4
) over the flue
gas pipe sealing collar. One of the jubilee clips must
clamp on the coupling of the flue gas collector and the
other onto the flue gas pipe.
z
Tighten the jubilee clips.
After the jubilee clips have been tightened the flue gas
pipe sealing collar must fit evenly and closely.
2.6.7
Fit the flue gas temperature sensor (Option)
z
Weld the coupling (Fig. 29,
Item 3
) at a distance of
2 x flue gas pipe diameter (A) – min. 720 mm – from
the flue gas collector into the flue gas pipe.
z
Install the flue gas temperature sensor (Fig. 29,
) in accordance with separate installation
instructions.
NOTE!
We recommend you use a flue gas pipe
sealing collar (Fig. 29, Item 1)
.
NOTE!
Re-tighten the jubilee clips a short time
after commissioning.
Fig. 29
Flue gas pipe installation
Item 1: Flue pipe sealing collar
Item 2: Flue gas temperature sensor
Item 3: Coupling
Item 4: Jubilee clip
Item 5: Flue gas collector
1
2
3
4
min. 720 mm
5