Liquid Propane conversion
Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
5
3
Liquid Propane conversion
To convert the boiler to liquid propane, the following
instructions must be adhered to:
3.1
Shut down the boiler
B
Turn off the gas supply underneath the boiler.
B
Switch off the boiler using the main switch (
Æ
fig. 1,
[1]).
B
Disconnect the electrical power to the boiler.
B
Set the thermostat or other operating control to lowest
setting.
Fig. 1
Mains switch
B
Open the boiler door by turning the vent key through
¼ rotation anti-clockwise(
Æ
fig. 2).
Fig. 2
Opening the boiler door
3.2
Changing the gas valve assembly
B
Loosen the screw connection on the gas valve
(
Æ
fig. 3, [1]) and pull the plugs (
Æ
fig. 3, [2]) from the
gas valve.
Fig. 3
Undoing the connections to the gas valve
B
Pull both plugs from the fan unit (
Æ
fig. 4, [1]).
Fig. 4
Removing the connectors from the fan
B
Pull the air suction tube from the fan (
Æ
fig. 5).
Fig. 5
Pulling the air suction tube from the fan
B
Loosen both retaining clips on the burner cover
(
Æ
fig. 6).
DANGER:
Risk of explosion.
B
Work on gas appliances must be carried
out by competent registered personnel.
Reset
0
1
140
130
120
90
100
110
Aut
0
Eco
190
170
150
130
90
110
Aut
0
6720615033-002.1TD
1
1.
2.
3.
6720615033-003.1TD
1
2
2
6720615033-004.1TD
1
1
6720615033-005.1TD
6720615033-006.1TD
Summary of Contents for GB162-80 kW
Page 12: ...6720615033 0004...