FM443 Function module - We reserve the right to make technical modifications.
34
The functions of the FM443
3
3.6.2
Setting reloading circ start-up
Reloading will be started as soon as a higher temperature is
measured on the FSS solar sensor than is set on the FB hot water
sensor.
Call up the service level.
Turn the dial until "service level – solar" appears on the display.
Press "Display" to select the main menu "SOLAR".
Turn the dial until "SOLAR DATA – reloading circ start-up
18°F" (10°C) appears on the display.
Press and hold the "Display" button and turn the dial.
You can now set the start-up temperature difference for the
reloading circulator.
SOLAR DATA
reloading circ
start-up
18°F
Input range
Factory setting
reloading circ start-up
9 °F – 27 °F (5 °C – 15 °C)
18 °F (10 °C)