2
Product Information
EM100 – 6720891034 (2019/04)
14
2.2.2 Flow temperature control
Linear relationship between the 0–10 V signal (U in volts) and
the required flow temperature
in °C with reference to the
minimum flow temperature range to the maximum flow
temperature range [default setting 20 to 90 °C]):
Fig. 2
Linear relationship between the 0–10 V signal (U in
volts) and the required flow temperature
in °C)
The connected heat sources are enabled and disabled
according to the required flow temperature.
2.3
Supplied parts
[1]
Module
[2]
Bag with strain relief
[3]
Installation Manual
2.4
Specification
This product conforms to European directives and
supplementary national requirements in design and
operation. Compliance is demonstrated by the CE
marking.
You can request the conformity declaration of the product. If
you require this, contact the address on the back cover of these
instructions.
Table 3
Table 4
Measurements of low loss header temperature
sensor (T0)
Specification
Dimensions
(W × H × D)
151 × 184 × 61 mm (for more
dimensions
Fig. 7 at end of
document)
Maximum conductor cross-
section
•
230 V terminal
•
2.5 mm
2
•
Extra-low voltage terminal •
1.5 mm
2
0010024409-001
/ °C
U / V
0,5
20
90
1
10
Rated voltages
•
BUS
•
15 V DC
(reverse polarity
protected)
•
Module mains voltage
•
230 V AC, 50 Hz
•
User interface
•
15 V DC
(reverse polarity
protected)
•
Pump, solenoid valve,
interference output
•
230 V AC, 50 Hz
Fuse
230 V, 5 AT
BUS interface
EMSand EMS plus
Power consumption –
Standby
< 3 W
Max. power output
•
per connection(PC0)
•
per connection(OE1)
•
400 W (high-efficiency
pumps permissible:
<30 A for 10 ms)
•
120 W (high-efficiency
pumps permissible:
< 30 A for 10 ms)
Permitted ambient
temperature
0 ... 60 °C
IP rating
IP 44
Protection class
I
ID no.
Data plate (
end of document)
°C
°C
°C
20
12486
50
3605
80
1256
25
10000
55
2989
85
1070
30
8060
60
2490
90
915
35
6536
65
2084
100
677
40
5331
70
1753
–
–
45
4372
75
1480
–
–
Specification