LRV lift control valve
Operation
300−I−9010212−E−10/08.08
5.1.4.2
Options menu (2)
Setting "Valve type"
S
Selection of valve type
S
Overwrites the current control parameters (PID) with the factory
settings for this valve
S
Setting range:
−
C−LRV 175
−
C−LRV 350
−
C−LRV 700
Setting "SIU type"
S
Off: monitoring is switched off
S
1: SIU−1, if the setting for the demand/feedback difference is
exceeded, then:
−
Lift is stopped with emergency−stop deceleration
−
The relay switches
⇒
−
LED SIU−1 lights
−
If the Relay function" setting is only SIU": reset operation after
there is no longer any travel command. Otherwise: delay of 2s.
S
4: SIU−4, if the speed setting (feedback threshold) is exceeded in the
door zone, then:
−
The relay switches
⇒
S
1+4: SIU−1 and SIU−4 active; functions as above
S
Standard: 1, i.e. SIU−1
Function
Display on Handterminal
none
Off
SIU−1
1
SIU−4
4
SIU−1 + SIU−4
1+4
Important
: there is no SIU−1 monitoring during inspection speed with
K5!