Assembly:
• Mount detector only in horizontal position.
• Produce drill holes for two screws M5 - according to the
hole layout from the smoke detector pedestal.
• Mount the smoke detector pedestal with two screws M5
at the mounting surface.
• Guide detector into locking position and turn it to the
right.
Maintenance:
• Check smoke detector regularly with testing gas.
Adhere to instructions for detector test.
•
Yellow
blinking of the
LED
-display indicates a fault.
• Clean dirty detectors with a moist cloth or a little rubbing
alcohol. Replace if necessary.
• For maintenance and change of the detector, note the
current regulations (e.g. DIN 14 675).
N
ote
Optical smoke detector with mounting base
Part.-No.:
60.300
Application
: for the automatic early detection of fire and controlling of the
„Emergency OPEN“ function via a detector line of RWA
Control Units.
Measuring element: photo electric / scattered light principle
Operating voltage: 8,5 – 33 V DC
Standby current: < 100 μA
Housing: Surface mounting, plastic (ABS), pearl white
Dimensions (ØxH): Ø100 x 50 mm
Connections: Screw terminals 1,0 mm² (rigid wire)
Protection rating: IP23D
Display: Alarm LED
VdS certification no.:
G 204039
Feature / Equipment:
• Fire algorithms to avoid false alarms, automatic alarm threshold tracking
• According to EN 54-7, connection to the detector line input
I
nstallatIon
and
C
ommIssIonIng
I
nstruCtIon
Optical smoke detector
!
!
!
Remove the dust protection cap only with
start-up.
The connection depends on the Control Unit.
The smoke detector must be disposed in
accordance with legal regulations.
Strictly observe the information given in this
and in the instructions for installation of the
RWA control unit, when mounting the
optical smoke detector
.
Details can be found on our website
www.btr-hamburg.de
Keep this instruction over the lifetime of the
product.
Warranty claims require proper and profes-
sional assembly, installation and maintenan-
ce in accordance with national regulations
and manufacturer‘s instructions of the RWA
control unit.
The safety instructions in the supplied pro-
duct documentation are to be observed.