50 kW DC Fast Charger
INSTALLATION AND USER’S MANUAL
Page
17
of
26
This document is the
Property of BTCPower Inc.
and shall not be
copied, reproduced, or used as the basis for sale or manufacture
of apparatus without written permission.
29-May-19
Initial Release
CAUTION
For 208 VAC equipment the phases used must each measure 120VAC to Neutral. Earth Ground
must be connected to Neutral at only one point, usually at the Service Entry of the Breaker
Panel.
Electrical Connection
Connect 3-Phase (208VAC or 480VAC) to the Mersen Terminal Block MPDB67013 in the lower
compartment of the 50kW DC Fast Charger.
MERSEN TERMINAL BLOCK (MPDB67013)
Line Side
Load Side
Amp Rating per Pole
Wire
Range
Opening
per Pole
Torque
(lb-in)
Wire
Range
Opening
per Pole
Torque
(lb-in)
Cu Wire
Al Wire
350
–
6
1
275
2/0
–
6
2
120
310 A
250 A
8
–
14
2
50
INSTALLATION