Block diagram

  

 

 

 

 
 
 
 
 

Mounting instructions

 

 
The  KLC  20  should  be  mounted  close  to  the  flame  with  straight  alignment.  The  compact  flame  detector 
should  be  mounted  with  the  mounting  flange  KLC  or  another  suitable  holder  with  Ø14  mm  opening.  The 
radial  adjustment  to  the  flame  is  realised  with  the  viewing  angle  adapter  KLC  and  replaces  the  mounting 
flange  KLC.  Fix  the  detector  with  the  holder.  The  best  flame  signal  will  be  achieved  from  strong  flickering 
parts  of  the  flame  radiation.  The  angle  of  view,  especially  with  sight  tubes,  must  be  of  appropriate 
dimensions to avoid any reduction of flame radiation. Protect the sensor against other light sources. 
 
To  avoid  any  disturbance,  do  not  align  the  detector  direct  to  the  ignition  spark.  Breakdowns  during  pre-
ventilation  procedure  may  occur.  The  maximum  length  of  the  connection  must  be  in  accordance  with  the 
technical data. Install the detector connection cable with most possible distance to the ignition cable. 
 
Attention: 

For safety reasons and technical regulations a controlled burner shut down of at 
least once per 24 hours must be guaranteed. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for KLC 20

Page 1: ...on to provide an output signal for burner control boxes All flam will be detected by an automatic sensitivity control Adjustments during commissioning and maintenance are not necessary Due to internat...

Page 2: ...ting condition typical 2 sec Switch On delay after Flame On typical 0 5 sec Switch Off time after Flame Off 0 5 sec max switching current 15 mA max switching power 0 3 W max switching voltage 280V AC...

Page 3: ...rong flickering parts of the flame radiation The angle of view especially with sight tubes must be of appropriate dimensions to avoid any reduction of flame radiation Protect the sensor against other...

Page 4: ...ment of the KLC is accomplished 20 to the flame axle The angle adapter replaces the mounting flange KLC Separate type of automatic flame guard is not necessary therefore With maintenance work the refl...

Page 5: ...Connector Diagram KLC 20 Control boxes Dungs Satronic Type of control box MPA 22 TF 8 DKO 9 DKW 9 DMO 9 TMO 720 4 Blue terminal no 12 5 N 2 2 2 Black terminal no 12 3 Ion 1 1 1 Brown terminal no 6 17...

Page 6: ...case the KLC 20 will switch the output a first but after a period of about 9 seconds the KLC 20 will switch the output off again During revision it has to be kept in mind that y is intended and no ma...

Page 7: ...ht 7 mm 665001010000 Mounting flange KLC overall height 13 mm 665002010000 Viewing angle adapter KLC Accessories for radial mounting applications 615001020000 ADP 11 UV Adapter for direct mounting app...

Page 8: ...on Worcester WR4 9ND Telephone 01905 457557 Fax 01905 759515 Email for sales sales heatsol co uk Email for technical advice info heatsol co uk BST Solutions GmbH Eggerscheidter Stra e 57 D 40883 Ratin...

Reviews: