background image

6.2 

The aperture must be ‘lined  out’. 

6.3 

Cut size = damper size + (2 x nominal gap size) + (2 x wall board thickness). 
E.g. for 150mm dia. damper, and 12.5mm wall board, cut aperture should be 
195mm (150+(2x10)+(2x12.5)) 

6.4 

Mark out position and size of required cut size on the wall. 

 

6.5 

Using appropriate means (e.g. jig saw), cut the aperture in the wall, removing 
each layer and any infill that is present 

6.6 

Cut 2 pieces of steel track 50mm+ longer than opening size. 

6.7 

Fit track to top and bottom of opening, screwing in position from both sides 
of wall  at  each  end  of  track  with drywall  screws  and at maximum  300mm 
centers. 

6.8 

Cut 2 more pieces of track, this time, equal opening size. 

6.9 

Fit  track  to  sides  of  opening,  screwing  in  position  in  a  similar  fashion  as 
above. 

6.10  Cut 4 pieces of board width to line the opening to the full width of the wall. 

Screw  each  baton  with  2  screws  to  the  track  that  is  lining  the  opening. 
Ensure the access side baton is flush with the surface of the  wall. 

6.11  Position the damper centrally in wall opening (width/height), with blade axle 

running horizontally. Using drywall screws, fix Installation Plate to wall using 
drywall screws. 

Important: 

Ensure the screws ‘pick up’ the track lining the 

aperture  so  that  the  proper  fire  integrity  of  the  installation  will  not  be 
compromised.  Use  either  one  of  the  two  appropriate  Ø5mm  corner  fixing 
holes and all Ø5mm mid-span fixing  holes. Note for damper sizes of 100mm 
– 200mm dia, the mid span fixing behind the fitted actuator, can be omitted. 

Block wall and Floor Installation 

 

 

 

6.12  Preferably,  prepare  opening  whilst  building  wall,  or  cut  opening  if  wall 

already exists. 

6.13  Cut size = finished  size 
6.14  E.g. for 250 dia. damper, cut aperture should be 270mm square (250+20) 
6.15  Mark out the position and size of opening on the wall. 
6.16  Using appropriate means, cut the aperture in the wall. 
6.17  Position  damper  centrally  in  wall  opening  with  blade  axle  running 

horizontally. Fix Installation Plate to wall. (See section 3) 

6.18  There are a variety of proprietary fixings available. Fixings must be fire rated 

(steel, NOT aluminum or plastic). Check minimum dimension specification 
between  fixing  and  edge  of  opening.  BSB  recommend  steel  anchor  type 
bolts Ø5mm minimum). 

6.19  Position the damper centrally in wall opening (width/height), with blade axle 

running  horizontally.  Using  steel  screws,  fix  Installation  Plate  to  wall 

Important: 

Use either one of the two appropriate Ø5mm corner fixing holes 

and  all  Ø5mm  mid-span  fixing  holes.  Note  for  damper  sizes  of  100mm  – 
200mm dia, the mid span fixing behind the fitted actuator, can be omitted. 

 

 

Obscured fixing hole behind 

actuator (see 6.11) 

38mm long drywall screws to affix installation 

plate to metal frame within drywall (see 6.11) 

 

No infill required in the void 

behind Installation Plate 

Steel fixings – refer to 6.19 

 

Summary of Contents for FSD-C

Page 1: ... equipment as necessary 3 2 8mm 10mm for motor fixing and 12mm AF spanners to change blade position via drive shaft Phillips 2 screwdriver for setting of OPEN position if required 3 3 Cordless drill 3 4 Screwdriver to suit junction box terminals 4 Preparation for Installation 4 1 Before installation the damper should be inspected to ensure that it has not been damaged and is in good condition foll...

Page 2: ... either one of the two appropriate Ø5mm corner fixing holes and all Ø5mm mid span fixing holes Note for damper sizes of 100mm 200mm dia the mid span fixing behind the fitted actuator can be omitted Block wall and Floor Installation 6 12 Preferably prepare opening whilst building wall or cut opening if wall already exists 6 13 Cut size finished size 6 14 E g for 250 dia damper cut aperture should b...

Page 3: ...ssembly and 8mm AF head screw 3Nm 7 7 Test refer to section 10 8 Setting of Damper mid set point Position optional 8 1 Dampers are supplied with actuators set to travel to fully open position by default 8 2 Optionally dampers can be set so that the open position is restricted to between 30 to 90 60 range This is for system air balancing purposes should it be required 8 3 To utilise set point posit...

Page 4: ...ition 10 9 If damper has seized 10 5 2 Open the damper even partially if possible Clean the inside of the damper case where the blade seals make contact Use a soft cloth with a light application of light lubricant Connect Duck Oil recommended 10 5 3 From the outside of the case lightly apply a light lubricant into blade axle bearings 10 5 4 Remove excess lubricant 10 5 5 It is important to log and...

Page 5: ...CTED BY Print name Signature Company Date Actuator mid point setting circle 30 35 40 45 50 55 60 65 70 75 80 85 90 THERMAL FUSE FITTED BY Print name Signature Company Date FAIL SAFE POSITION POWER OFF position Tick appropriate box CLOSED default OPEN non std FINAL INSPECTION BY Print name Signature Company Date Rev 2 May 2020 BSB Engineering Services Ltd Tel 44 0 1795 422609 Email enquiries bsb da...

Reviews: