Table AN — 581J*14 3 Phase 12.5 Ton Vertical Supply — Belt Drive Fan Performance
NOTES:
1. For more information, see fan performance notes on page 94.
2.
Boldface
indicates field-supplied drive is re
q
uired.
FAN PERFORMANCE NOTES:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure
caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories may add
static pressure losses. Selection software is available, through your salesperson, to help you select the best motor/drive combina-
tion for your application.
4. The fan performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would work,
Bryant recommends the lower horsepower option.
5. For information on the electrical properties of Bryant motors, please see the Electrical Data section of this unit’s product data.
6. For more information on the performance limits of Bryant motors, see the application data section of this unit’s product data.
7. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors. Motors regu-
lated by EPACT include any general purpose, T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase,
squirrel cage induction motors of NEMA (National Electrical Manufacturers Association) design A and B, manufactured for use
in the United States. Ranging from 1 to 200 Hp, these continuous-duty motors operate on 230 and 460 volt, 60 Hz power. If a
motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance requirements.
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3438
431
0.59
504
0.81
574
1.08
643
1.40
706
1.74
3750
456
0.71
524
0.95
589
1.22
653
1.54
715
1.90
4063
481
0.86
546
1.11
606
1.39
666
1.71
725
2.07
4375
507
1.03
569
1.30
626
1.59
681
1.91
736
2.27
4688
533
1.22
593
1.51
647
1.81
698
2.13
750
2.49
5000
560
1.44
617
1.74
669
2.05
718
2.39
766
2.75
5313
587
1.68
642
2.00
691
2.33
738
2.67
784
3.04
5625
614
1.95
667
2.29
715
2.63
760
2.99
804
3.36
5938
642
2.25
692
2.60
739
2.97
782
3.34
824
3.72
6250
670
2.58
718
2.95
763
3.33
805
3.72
846
4.11
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
3438
763
2.10
815
2.46
862
2.82
905
3.18
946
3.55
3750
772
2.28
825
2.66
873
3.05
918
3.45
959
3.84
4063
781
2.46
834
2.87
883
3.29
929
3.71
971
4.14
4375
790
2.66
843
3.09
892
3.53
938
3.98
982
4.43
4688
801
2.89
852
3.32
901
3.78
947
4.25
991
4.73
5000
814
3.15
863
3.58
910
4.04
956
4.53
999
5.03
5313
830
3.44
875
3.87
920
4.33
965
4.83
1008
5.34
5625
847
3.77
890
4.20
933
4.66
975
5.15
1017
5.67
5938
865
4.13
906
4.56
947
5.03
987
5.52
1028
6.04
6250
885
4.53
924
4.97
962
5.43
1001
5.92
—
—
Standard static 440-609 RPM, 2.9 bhp max
Medium static 609-778 RPM, 3.7 bhp max
High static 776-955 RPM
Voltage: 208-v / 230-v / 460-v / 575-v
Max bhp: 6.5 / 6.9 / 7.0 / 8.3
APPENDIX C — FAN PERFORMANCE
Summary of Contents for Preferred 581J04-14
Page 36: ...36 Fig 60 Integrated Gas Control IGC Board RED LED STATUS ...
Page 44: ...44 Fig 65 RTU Open Overlay for Economizer Wiring ...
Page 45: ...45 Fig 66 VFD Overlay for W2770 Controller Wiring ...
Page 100: ...100 Fig F 581J 08 09 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 101: ...101 Fig G 581J 11YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 102: ...102 Fig H 581J 12 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 103: ...103 Fig I 581J 04 06 YAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 104: ...104 Fig J 581J 04 06 YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 105: ...105 Fig K 581J 04 06 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 108: ...108 Fig N 581J 07 12A B C YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 109: ...109 Fig O 581J 07 12A B C YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 110: ...110 Fig P 581J 08 09 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 111: ...111 Fig Q 581J 08 09 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 112: ...112 Fig R 581J 11 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 113: ...113 Fig S 581J 11 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 114: ...114 Fig T 581J 11 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 115: ...115 Fig U 581J 12 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 116: ...116 Fig V 581J 12 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 117: ...117 Fig W 581J 14 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 118: ...118 Fig X 581J 14 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 119: ...119 Fig Y 581J 14 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 120: ...120 Fig Z 581J 14 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 143: ...143 Fig AW RTU Open Wiring Diagram APPENDIX D WIRING DIAGRAMS ...