65
APPENDIX C — FAN PERFORMANCE
549K*06N THREE PHASE — 5 TON VERTICAL SUPPLY (RPM - BHP)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1500
1228
0.20
1394
0.29
1554
0.40
1701
0.53
1836
0.66
1625
1305
0.24
1457
0.33
1609
0.44
1750
0.57
1882
0.71
1750
1384
0.28
1523
0.37
1666
0.49
1802
0.62
1930
0.76
1875
1466
0.33
1592
0.43
1726
0.54
1857
0.67
1981
0.82
2000
1549
0.39
1664
0.48
1789
0.60
1914
0.74
2034
0.88
2125
1633
0.46
1739
0.55
1855
0.67
1974
0.81
2089
0.95
2250
1718
0.53
1816
0.63
1924
0.74
2036
0.88
2146
1.03
2375
1803
0.61
1894
0.71
1995
0.83
2100
0.97
2206
1.12
2500
1890
0.70
1974
0.80
2068
0.92
2167
1.06
2268
1.21
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1500
1961
0.80
2079
0.96
2191
1.12
2297
1.29
2399
1.47
1625
2004
0.85
2120
1.01
2230
1.18
2334
1.35
2434
1.53
1750
2050
0.91
2163
1.07
2270
1.24
2373
1.41
2472
1.60
1875
2098
0.97
2208
1.13
2314
1.31
2414
1.48
2511
1.67
2000
2148
1.04
2256
1.21
2359
1.38
2458
1.56
2553
1.75
2125
2200
1.11
2305
1.28
2407
1.46
2504
1.64
2597
1.83
2250
2254
1.20
2357
1.37
2456
1.55
2551
1.73
2643
1.93
2375
2310
1.28
2410
1.46
2507
1.64
2600
1.83
2690
2.03
2500
2368
1.38
2465
1.56
2560
1.75
2651
1.94
2739
2.14
Standard Static 1228-2150 RPM, 1.06 Max BHP
Medium Static 1228-2390 RPM, 1.44 Max BHP
High Static 1228-2836 RPM, 2.43 Max BHP
549K*06N THREE PHASE – STANDARD STATIC — 5 TON VERTICAL SUPPLY (RPM - VDC)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
Vdc
RPM
Vdc
RPM
Vdc
RPM
Vdc
RPM
Vdc
1500
1227
5.7
1394
6.5
1554
7.2
1701
7.9
1835
8.5
1625
1305
6.1
1456
6.8
1609
7.5
1750
8.1
1881
8.7
1750
1385
6.4
1523
7.1
1666
7.7
1802
8.4
1930
9.0
1875
1466
6.8
1592
7.4
1726
8.0
1857
8.6
1981
9.2
2000
1549
7.2
1664
7.7
1789
8.3
1914
8.9
2034
9.5
2125
1632
7.6
1739
8.1
1855
8.6
1974
9.2
2089
9.7
2250
1718
8.0
1816
8.4
1924
8.9
2035
9.5
2146
10.0
2375
1803
8.4
1894
8.8
1994
9.3
2100
9.8
—
—
2500
1890
8.8
1974
9.2
2068
9.6
—
—
—
—
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
Vdc
RPM
Vdc
RPM
Vdc
RPM
Vdc
RPM
Vdc
1500
1961
9.1
2079
9.7
—
—
—
—
—
—
1625
2004
9.3
2120
9.9
—
—
—
—
—
—
1750
2050
9.5
—
—
—
—
—
—
—
—
1875
2097
9.8
—
—
—
—
—
—
—
—
2000
2147
10.0
—
—
—
—
—
—
—
—
2125
—
—
—
—
—
—
—
—
—
—
2250
—
—
—
—
—
—
—
—
—
—
2375
—
—
—
—
—
—
—
—
—
—
2500
—
—
—
—
—
—
—
—
—
—
Standard Static 1227-2150 RPM
Summary of Contents for Preferred 549K 04-06
Page 84: ...84 APPENDIX D WIRING DIAGRAMS Fig F 549K 04 06 Power Wiring Diagram 208 230 1 60...
Page 85: ...85 APPENDIX D WIRING DIAGRAMS Fig G 549K 04 06 Power Wiring Diagram 208 230 3 60...
Page 86: ...86 APPENDIX D WIRING DIAGRAMS Fig H 549K 04 06 Power Wiring Diagram 460 575 3 60...
Page 89: ......