background image

8

The compressor will always start unloaded and stay unloaded for

five seconds even when the thermostat is calling for high stage

capacity.

Quiet Shift

2

Quiet shift

2 is a field selectable defrost mode (factory set to OFF),

which will reduce the occasional noise that could be heard at the

start of defrost cycle and restarting of heating cycle. It is selected

by placing DIP switch 3 on defrost board in the ON position.
When Quiet Shift

2 switch is placed in ON position, and defrost is

initiated, the following sequence of operation will occur: The

compressor will be de

energized for approximately 1 minute, then

the reversing valve will be energized.  A few seconds later, the

compressor will be re

energized and the normal defrost cycle

starts.
Once defrost termination conditions have been met, the following

sequence will occur: The compressor will be de

energized for

approximately 1 minute, then the reversing valve will be

de

energized. A few seconds later, the compressor will be

re

energized and the normal heating cycle starts.

Defrost

The defrost control is a time/temperature control which has field

selectable settings of  30, 60,  90, or 120 minutes, factory set to 90

minutes. These settings represent the amount of time that must pass

after closure of the defrost thermostat before the defrost sequence

begins.
The defrost thermostat senses coil temperature throughout the

heating cycle. When the coil temperature reaches the defrost

thermostat setting of approximately 32

_

F (0

_

C), it will close,

which energizes the DFT terminal and begins the defrost timing

sequence. When the DFT has been energized for the selected time,

the defrost cycle begins.  Defrost cycle is terminated when defrost

thermostat opens, or automatically after 10 minutes.

Defrost Speedup

To initiate a forced defrost, speedup pins (J1) must be shorted with

a flat head screwdriver for 5 seconds and

 RELEASED

. If the

defrost thermostat is open, a short defrost cycle will be observed

(actual length depends on Quiet Shift

2 switch position). When

Quiet Shift

2 is off, only a short 30 second defrost cycle is

observed. With Quiet Shift

2 ON, the speedup sequence is

approximately 3 minutes; 1 minute compressor off period followed

by 30 seconds of defrost with compressor operation. When

returning to heating mode, the compressor will turn off for an

additional 1 minute.
If the defrost thermostat is closed, a complete defrost cycle is

initiated. If the Quiet Shift

2 switch is turned on, the compressor

will be turned off for two 1 minute intervals as explained

previously.

OF2

O

F1

ON

QUIET

SHIFT

120

30

60

60

30

90

INTER

V

AL  

TIMER

OFF

P3

DFT

O   R   

W

2

   

Y   C

T2 C  C  O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A05378

Fig. 11 

 

Defrost Control

Check Charge

NOTE

:  

CHARGE IN HIGH STAGE ONLY.

Factory charge amount and desired subcooling are shown on unit

rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be

favorable for subcooling charging. Favorable conditions exist

when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15ft  (4.57 m) of lineset. Adjust charge

by adding or removing 0.6 oz/ft  (.018 kg/m) of 3/8 liquid line

above or below 15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow

system to operate in cooling mode at least 15 minutes. If conditions

are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a properly

charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge

by weight based on line length and allow the indoor temperature to

drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15ft (4.57 m) only. Charge level should then

be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

:  If line length is beyond 80 ft (24.38 m) or greater than 20

ft (6.10 m) vertical separation,  See Long Line Guideline for
special charging requirements.

Heating Check Chart Procedure

To check system operation during heating cycle, refer to the

Heating Check Chart on outdoor unit. This chart indicates whether

a correct relationship exists between system operating pressure and

air temperature entering indoor and outdoor units. If pressure and

temperature do not match on chart, system refrigerant charge may

not be correct. Do not use chart to adjust refrigerant charge.

Verify units for proper switching between low & high
stages

Check the suction pressures at the service valves.   Suction pressure

should be reduced by 3

10% when switching from low to high

capacity.
Compressor current should increase 20

45% when switching from

low to high stage.   The compressor solenoid when energized in

high stage, should measure 24vac at leads inside control box.
When the compressor is operating in low stage the 24v DC

compressor solenoid coil is de

energized.  When the compressor is

operating in high stage, the 24v DC solenoid coil is energized.  The

solenoid plug harness that is connected to the compressor HAS an

internal rectifier that converts the 24v AC signal to 24v DC.  

DO

NOT INSTALL A PLUG WITHOUT AN INTERNAL

RECTIFIER.

226A

Summary of Contents for PREFERRED 226A Series

Page 1: ...a suitable warning label EXPLOSION HAZARD Failure to follow this warning could result in death serious personal injury and or property damage Never use air or gases containing oxygen for leak testing...

Page 2: ...luding adverse weather conditions Clearance Requirements When installing allow sufficient space for airflow clearance wiring refrigerant piping and service Allow 24 in 609 6 mm clearance to service en...

Page 3: ...n 914 4 mm Outdoor units may be connected to indoor section using accessory tubing package or field supplied refrigerant grade tubing of correct size and condition For tubing requirements beyond 80 ft...

Page 4: ...be BEFORE bolting adapter to valve This helps prevent overheating and damage to plastic washer or o ring For Vapor Service Valve remove valve core from schrader port on Service Valve BEFORE brazing Th...

Page 5: ...isconnect through power wiring hole provided and into unit control box Connect Ground and Power Wires WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or...

Page 6: ...Below is a brief summary of the furnace airflow configurations 1 The Y2 call for high stage cooling energizes the Cool tap on the control board The grey wire from cool tap is connec ted to tap 5 on t...

Page 7: ...ff Cooling With first stage cooling Y and O are powered on and with second stage cooling Y2 Y and O are powered on The O energizes the reversing valve switching it to cooling position The Y signal sen...

Page 8: ...E IN HIGH STAGE ONLY Factory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit To properly check or adjust charge conditions...

Page 9: ...s and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with owner Explain system opera tion and periodic maintenance requirements outlined in manual 5 Fil...

Page 10: ...install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all...

Reviews: