At the time of air purifier cartridge replacement, if a powdery
residue is noticed on the tips of the points in the ionization
array, proceed to clean them by completing the following
steps:
Step 1

Turn the heating and cooling system power off.

ELECTRICAL SHOCK AND HIGH VOLTAGE

HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system. There may be more than one (1) disconnect

switch.

!

WARNING

Step 2

Turn the Perfect Air

t

Air Purifier switch to the off

position.

Step 3

Remove the Perfect Air

t

Air Purifier door.

Step 4

Unplug the power cord and flow sensor cable (if

connected) from the enhancement module 9 ( See Fig. 7 and 8)

Step 5

Slide out the enhancement module assembly and safety

screen.

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing and gloves when

handling parts.

!

WARNING

Step 6

Slide out the Safety Screen and set aside.

NOTE

: Best cleaning tools: 5 inch handle paint brush with 2

inch width (or greater) brush point (synthetic or natural bristle)
(See Fig. 14) or vacuum cleaner with brush attachment.

Step 7

Gently stroke the ionization pins on the top plane of

each bar with enough brush depth to hit front and back tips of the
points in the ionization array. Use a gentle back and forth
brushing motion to clean any small accumulations from the tips
of the points. If desired, use vacuum cleaner with brush
attachment to gently vacuum the frame and components of
enhancement module.

Step 8

Reinstall the Safety Screen.

Step 9

Slide in enhancement module.

Step 10

Reconnect the power cord and flow sensor cable.

Step 11

Replace the Perfect Air

t

Air Purifier Door

Step 12

Turn the Perfect Air

t

Air Purifier switch to the on

position.

Step 13

Turn heating and cooling system power on.

30°

POINTS ARE SHARP! BE VERY CAREFUL DURING CLEANING.

Tip of point with residue

Tip of point after cleaning

A06671

Fig. 14

---

Removal of Deposits from Ionization Pins

GAP

A

B

Summary of Contents for PERFECT AIR 1620

Page 1: ...CSA certified for shock and electrical fire hazard only La Perfect Airt Air Purifier certification CSA vise uniquement les risques de choc electrique et A06367 Fig 1 GAPAB Unit SAFETY CONSIDERATIONS I...

Page 2: ...recommended and a standard disposable furnace filter should be mounted between the humidifier and the air purifier to trap hard water salt deposits and water droplets Transitions If the return air du...

Page 3: ...Purifier or door can be rotated 180_ to accommodate the cabinet orientation c The location of the Perfect Airt Air Purifier should be readily accessible Enough room should be provided for periodic rep...

Page 4: ...work See Fig 6 h Seal seams with tape or caulking after the Perfect Airt Air Purifier cabinet has been secured ELECTRICAL SHOCK AND HIGH VOLTAGE HAZARD Failure to follow this warning could result in...

Page 5: ...bag With the bypass jumper in place the air purifier will be on at all times when connected to electrical line power see Fig 10 d Attach the quick connect terminals to the fused power connector leads...

Page 6: ...OWER CONNECTION TO L2 FIELD POWER SUPPLY TO L1 FIELD POWER SUPPLY 5 AMP IN LINE FUSES GROUND ATTACH TO FAN COIL GROUND CHASSIS CABLE CONNECTOR TO SECURE POWER CORD TO FAN COIL CABINET A06515 Fig 10 Fa...

Page 7: ...her the TrueSenset dirty filter algorithm or time The installer should use their discretion to select the most appropriate option based on the initial system static pressure Step 3 Maximizing Performa...

Page 8: ...iate protective clothing and gloves when handling parts WARNING Step 6 Slide out the Safety Screen and set aside NOTE Best cleaning tools 5 inch handle paint brush with 2 inch width or greater brush p...

Page 9: ...position Step 3 Confirm that the fan coil blower is operating Step 4 Confirm that 208 230 VAC power is provided Attach power supply connector to the air purifier when the fan coil blower is operating...

Page 10: ...mum Airflow CFM 1350 1800 2000 Efficiency Equivalent to MERV 15 Equivalent to MERV 15 Equivalent to MERV 15 Replacement Cartridge GAPCBBAR1620 GAPCBBAR2020 GAPCBBAR2420 Initial Pressure Drop in w c at...

Page 11: ...ough a registered servicing dealer for credit 4 All work shall be performed during normal working hours LIMITATIONS OF WARRANTIES ALL IMPLIED WARRANTIES AND OR CONDITIONS INCLUDING IMPLIED WARRANTIES...

Page 12: ...change at any time specifications or designs without notice and without incurring obligations EBryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 02 0...

Reviews: