14
H — Reversing valve output (O/W2/B) is energized when HEAT mode is selected.
C — Reversing valve output (O/W2/B) is energized when COOL mode is selected.
Default is C.
Option 11 -- Minimum Deadband Between Heating And Cooling
Selections:
01 through 06 — Default is 02.
Sets the minimum allowable number of degrees between heating and cooling
setpoints. One setpoint will “push” the other to maintain this difference.
Option 12 -- Smart Recovery (programmable model only)
Selections:
OF, 30, 60, 90 — Default is 90.
Smart Recovery OF means setpoints change immediately at a program schedule
change. Thirty, 60, or 90 selects the number of minutes recovery starts before
programmed recovery time. Recovery takes place smoothly during the selected
recovery time, ending at the recovery time and temperature which is programmed.
If the setpoint is changed during smart recovery, the smart recovery is cancelled and
the new setpoint is effective immediately. Not available with non--programmable
thermostats.