background image

On a section of wall without pipes or duct work.

Thermidistat Control should NOT be mounted:

Close to a window, on an outside wall, or next to a door leading
to the outside.

Exposed to direct light and heat from a lamp, sun, fireplace, or
other temperature-radiating object which may cause a false
reading.

Close to or in direct airflow from supply registers and return-air
registers.

In areas with poor air circulation, such as behind a door or in
an alcove.

II.

SET DIP SWITCHES

There is a 4 section DIP switch within the Thermidistat Control
which must be properly set by the installer. It is easiest to set these
4 switches before the Thermidistat Control is mounted to the wall,
so STOP and complete the following steps:

1. Open hinged Thermidistat Control cover.

2. Remove cover completely by snapping it apart at hinge.

3. Open Thermidistat Control by pressing back half of the

right end of plastic case inward while, at the same time,
pulling front and back halves apart at the right end. The 2
halves will swing apart.

4. Snap hinge apart to completely separate the 2 halves.

5. Switches are located in upper right corner of circuit board.

To change switch position, use corner of a small screw-
driver to slide switch to opposite position.

6. After switches have been set, do not reassemble the 2

halves. The rear plastic will be first mounted to wall.

A.

Switch 1—AC/HP Select

Use this switch to select between air conditioner and heat pump
systems.

TO SET:
OFF—for air conditioner installations. This is factory default.
ON—for heat pump installations, using either a fan coil or furnace
(dual fuel).

B.

Switch 2—1 Speed/2 Speed

This switch tells the system whether the compressor is 1 or 2
speed.

TO SET:
OFF—for single-speed compressor. This is factory default.
ON—for 2-speed compressors, whether AC or HP.

C.

Switch 3—Smart/Conventional Recovery

Selects between conventional and smart recovery from setback.
Conventional recovery changes to new set point at programmed
time. Smart recovery, which is active in both heating and cooling,
starts 90 minutes earlier and smoothly adjusts set point so room
will arrive at programmed temperature at programmed time.

TO SET:
OFF—for smart recovery. This is factory default.
ON—for conventional recovery.

D.

Switch 4—Installer Test OFF/ON

Selects a special installer test mode which assists with checkout
and troubleshooting. See Step 5.

TO SET:
OFF—for normal operation. This is factory default.
ON—for installer test mode.

III.

INSTALL THERMIDISTAT CONTROL

WARNING:

Before installing Thermidistat Control,

turn off all power to equipment. There may be more than
1 power disconnect. Electrical shock can cause personal
injury or death.

1. Turn off all power to equipment.

2. If an existing thermostat is being replaced:

a. Remove existing thermostat from wall.

b. Disconnect wires from existing thermostat, 1 at a time.

c. As each wire is disconnected, record wire color and

terminal marking.

d. New or additional wire may be needed to accommodate

added humidity outputs.

e. Discard or recycle old thermostat.

NOTE:

Mercury is a hazardous waste and MUST be disposed of

properly.

3. Select Thermidistat Control rear plastic. (If it is not sepa-

rated from the remainder of the Thermidistat Control, refer
to Step 2 above.)

4. Route wires through large hole in rear plastic. Level rear

plastic against wall (for aesthetic value only—Thermidistat
Control need not be leveled for proper operation) and mark
wall through 2 mounting holes.

5. Drill two 3/16-in. mounting holes in wall where marked.

6. Secure rear plastic to wall with 2 screws and anchors

provided. Additional mounting holes are available for more
secure mounting if needed. Make sure all wires extend
through hole in mounting base.

7. Adjust length and routing of each wire to reach proper

connector block and terminal on rear plastic with 1/4-in.
extra length. Strip only 1/4 in. of insulation from each wire
to prevent adjacent wires from shorting together when
connected.

8. Match and connect equipment wires to proper terminals of

each connector block. (See Table 6 and Wiring Diagrams
Fig. 3 through 30.) Remember R and C must be connected
for proper operation.

CAUTION:

Improper wiring or installation may damage

Thermidistat Control. Check to make sure wiring is
correct before proceeding with installation or turning on
power.

9. Push any excess wire into wall and against rear plastic. Seal

hole in wall to prevent air leaks. Leaks can affect operation.

10. Reattach Thermidistat Control body to rear plastic by first

reattaching hinge.

11. Close Thermidistat Control assembly, making sure pins on

back of circuit board align with sockets in connector.

12. Turn on power to equipment.

On power up, all display segments will light for 5 sec. For the next
5 sec, a 2-digit code appears on large display which identifies
Thermidistat Control configuration:

1. AC—for 1-speed air conditioner

2. HP—for 1-speed heat pump

3. A2—for 2-speed air conditioner

4. H2—for 2-speed heat pump

—2—

Summary of Contents for II TSTAT-0-16

Page 1: ...mable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal mem...

Page 2: ...O SET OFF for normal operation This is factory default ON for installer test mode III INSTALL THERMIDISTAT CONTROL WARNING Before installing Thermidistat Control turn off all power to equipment There...

Page 3: ...small display and available selections within each option large display D Configuration Options Selection OPTION 1 ANTICIPATOR ADJUSTMENT This adjustment controls sensitivity and cycle rate of Thermi...

Page 4: ...ll Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode...

Page 5: ...ons 1 2 and 3 For most heaters W1 is lower wattage heater and W2 is higher although some have equal elements for W1 and W2 Consult fan coil heater combination for the actual wattage connected to each...

Page 6: ...ould be considered permanent Once the change to non programmable operation is done a procedure is not provided to easily change it back Should this change be needed it is best to trade the Thermidista...

Page 7: ...he U S Department of Energy for both heating and cooling These provide energy saving tempera ture settings Refer to Table 3 If programmed schedule is to be used make sure HOLD icon is off This feature...

Page 8: ...equipment type and dehumidify selection choice The 3 available selections are described below The amount of extra dehumidification available is very dependent on the type of equipment in the home With...

Page 9: ...n on high humidity thus removing a 24 vac signal to initiate dehumidification Equip ment has been designed to operate in this manner so the Thermidistat Control must now accommodate the existing equip...

Page 10: ...TEM PERATURE button C Fifteen Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning on until preceding stage has been on for 15 minutes This timer is...

Page 11: ...TDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 1 6 13 and 15 Fig 6 Typical Fan Coil With 2 Speed Heat Pump A97385 O W2 Y1 W2 W W1 G R E W3 THERMIDISTAT TYPICAL FAN COIL 2 SPEE...

Page 12: ...1 2 6 13 and 15 REMOVE J2 JUMPER FOR HEAT STAGING REMOVE J1 JUMPER FOR DEHUMIDIFY MODES Fig 10 FK Series Fan Coil With 2 Speed Heat Pump A98281 O W2 W W1 Y1 W2 G R O Y1 THERMIDISTAT FK SERIES FAN COIL...

Page 13: ...OUTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR Fig 14 Single Stage Furnace With 2 Speed Heat Pump Dual Fuel A97394 O W2 W W1 Y1 W2 G R THERMIDISTAT 1 STAGE FURNACE 2 SPEED HEAT PUMP W...

Page 14: ...UTDOOR SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 13 and 15 Fig 18 Two Stage Furnace With 2 Speed Heat Pump Dual Fuel A97398 O W2 W W1 Y1 W2 G R THERMIDISTAT 2 STAGE FURNACE 2...

Page 15: ...SOR CONNECTIONS Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 12 13 and 15 Fig 22 Variable Speed 2 Stage Non Condensing Furnace With 2 Speed Heat Pump Dual Fuel A97437 O W2 W W1 Y1 W2 G R THERM...

Page 16: ...NNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 and 15 DH HUM Fig 26 Variable Speed 2 Stage Condensing Furnace Without DE Connection With 2 Speed Heat Pump Dual Fuel A97421 O W2 W...

Page 17: ...R SENSOR CONNECTION Y Y2 HUMIDIFIER 24 VAC OUTDOOR SENSOR See notes 6 10 11 13 15 and 18 Fig 30 Variable Speed 2 Stage Condensing Furnace With DE Connection With 2 Speed Heat Pump A98285 O W2 Y1 W2 W...

Page 18: ...attached in all dual fuel applications 10 Refer to indoor equipment Installation Instructions for proper setup 11 To activate dehumidify feature on older style variable speed furnaces Bryant 335MAV t...

Page 19: ...ed recovery time and gradually adjusts room temperature so desired temperature will be achieved at selected recovery time The fixed time period is 1 5 hr It operates in both heating and cooling This o...

Page 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: