30
GT060
Part
Load
30°
7.0
68-84
256-313
5-7
19-23
14.0
73-89
261-319
4-5
20-25
40°
7.0
113-138
172-210
18-22
19-23
81-99
277-339
7-8
22-26
14.0
110-134
161-196
12-14
20-24
86-105
283-346
5-6
23-28
50°
7.0
116-142
206-252
17-21
19-23
93-114
299-365
8-9
24-29
14.0
112-137
193-236
12-14
19-24
99-121
305-373
6-7
25-31
60°
7.0
118-145
241-294
17-21
18-23
106-129
321-392
9-11
26-32
14.0
115-140
225-275
11-14
19-23
113-138
327-400
7-8
28-34
70°
7.0
121-148
275-336
17-21
18-22
118-145
342-418
10-12
29-35
14.0
117-143
257-314
11-14
19-23
126-154
349-427
8-9
30-37
80°
7.0
123-151
309-378
16-20
18-22
131-160
364-444
11-14
31-38
14.0
120-146
289-353
11-13
19-23
139-170
371-454
8-10
33-40
90°
7.0
126-154
344-420
16-20
18-22
143-175
385-471
12-15
33-41
14.0
122-149
321-392
11-13
18-22
152-186
393-480
9-11
35-43
100°
7.0
128-157
378-462
16-19
17-21
14.0
125-152
353-432
11-13
18-22
GT060
Full
Load
30°
7.0
68-84
256-313
5-7
19-23
14.0
73-89
261-319
4-5
20-25
40°
7.0
117-143
182-222
15-19
21-26
81-99
277-339
7-8
22-26
14.0
114-139
170-208
11-14
22-27
86-105
283-346
5-6
23-28
50°
7.0
120-147
215-263
15-18
20-25
93-114
299-365
8-9
24-29
14.0
117-143
201-246
11-14
21-26
99-121
305-373
6-7
25-31
60°
7.0
123-150
248-304
14-17
20-24
106-129
321-392
9-11
26-32
14.0
119-146
232-284
11-13
21-25
113-138
327-400
7-8
28-34
70°
7.0
126-154
282-344
14-17
19-24
118-145
342-418
10-12
29-35
14.0
122-149
263-322
10-13
20-25
126-154
349-427
8-9
30-37
80°
7.0
129-157
315-385
13-16
19-23
131-160
364-444
11-14
31-38
14.0
125-153
294-360
10-12
19-24
139-170
371-454
8-10
33-40
90°
7.0
132-161
348-426
13-16
18-22
143-175
385-471
12-15
33-41
14.0
128-156
326-398
10-12
19-23
152-186
393-480
9-11
35-43
100°
7.0
134-164
382-466
12-15
17-21
14.0
131-160
357-436
9-11
18-22
Operating Temperatures and Pressures
COOLING
HEATING
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as
a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º
w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid
temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development,
specifications are subject to change without notice.