background image

 

7

 

a 3-amp automotive type fuse on the 
furnace control board.) Has a circuit 
breaker tripped?

• Is the manual shutoff valve in the gas 
supply pipe leading to the furnace 
open? Does the lever point in the same 
direction that the pipe runs (open)? Or 
is it at right angles (closed)?

 

NOTE: 

 

Before proceeding with the 

next checks, turn OFF the electrical 
power supply to the furnace. Remove 
the access doors.

• Is the control knob or switch on the 
gas valve turned to the ON position? If 
this or the preceding check shows an 
interruption in the gas supply, make 
sure the gas has not been shut off for 
safety reasons. If nothing else seems to 
be wrong, follow the startup proce-
dures found on pages 3, 4, and 5 of this 
user’s manual.

• If for some reason the vent is 
blocked, the draft safeguard switch or 
blocked vent shutoff switch (when 
used) will shut off the furnace. Reset 
the switch by pushing the button 
located on the switch. (See page 2 
for switch location.)

If the switch trips a second time, 
turn off the furnace and call for 
service.

• If your furnace still fails to operate, 
call your servicing dealer for trouble-

shooting and repairs. Tell your dealer 
the model and serial numbers for your 
furnace. (You should have them 
recorded on page 8 of this booklet.) 
By knowing exactly which furnace you 
have, the dealer may be able to offer 
suggestions over the phone, or save 
valuable time through knowledgeable 
preparation for the service call.

 

REGULAR DEALER 
MAINTENANCE

 

In addition to the type of routine main-
tenance you might be willing to do, 
your furnace should be inspected 
regularly by a properly trained service 
technician. An annual inspection (or 
biennial inspection, at least) should 
include the following:

1. Inspection of all combustion prod-

uct passages—including the burn-
ers, heat exchanger, inducer, and 
vent pipe.

2. Inspection of all combustion air

and ventilation air passages and 
openings.

3. Close check of all gas pipes 

leading to (and inside of) your 
furnace for leaks.

4. Inspection, cleaning, and lubrica-

tion (when required) of the blower 
motor and wheel.

 

NOTE:

 

 Refer to the unit Service Proce-

dures for blower motor oiling infor-ma-
tion. When required, the motor should  
be oiled by a qualified service techni-
cian. (Wrong oil type or excessive oil is 
detrimental to the motor.)

5. Routine inspection and cleaning/

replacement of the air filter.

6. Inspection of all supply- and 

return-air ducts for obstructions, 
air leaks, and insulation. Any 
problems found should be resolved 
at this time.

7. Inspection of furnace installation 

for proper support and any obvious 
deterioration of the furnace. The 
support must be sound and without 
sags, gaps, cracks, etc., around the 
furnace base so as to provide an 
air seal between the support and 
furnace.

8. A check for loose connections 

attaching individual components. 
Inspection of all electrical wiring 
and their connections.

9. Operational check of the furnace 

itself to determine working condi-
tion. Repair or adjustment should 
be made at this time.

Ask your servicing dealer for further de-
tails about an economical service con-
tract that covers seasonal inspections.

Summary of Contents for GAS-FIRED INDUCED-COMBUSTION FURNACE 393AAV

Page 1: ...ectrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in this manual is not followed exactly a fire or explos...

Page 2: ...rs went into the development of your new furnace Take a little time now to assure its most efficient operation for years to come 1 MODEL 393AAV Upflow Furnace 2 11 1 10 12 3 4 8 7 5 13 9 6 2 14 17 15 16 UPFLOW FURNACE COMPONENTS Inducer Rating Plate Model and Serial No Gas Valve Control Knob or Electric Switch On Off Gas Valve Gas Burner Flame Sensor Air Filter Retainer Air Filter Blower and Blowe...

Page 3: ...d electrical components Only trained and qualified personnel should install repair or service heating equipment Untrained personnel can perform basic maintenance functions such as clean ing and replacing air filters All other operations must be performed by trained service personnel Observe safety precautions in this manual on tags and on labels attached to the fur nace and other safety precaution...

Page 4: ...xternal manual gas valve See Fig 15 10 Set the room thermostat to a tem perature slightly above the room temperature This will automati cally signal the furnace to start The inducer motor will start and the hot surface ignitor will energize When hot the ignitor will have an orange glow 9 10 11 CL O S E FF O O F F 2 3 1 M P ON O F F C ON 12 11 After 32 to 70 sec the gas valve permits gas to flow to...

Page 5: ...Fig 13 7 If the furnace is being shut down because of a malfunction call your dealer as soon as possible PERFORMING ROUTINE MAINTENANCE With the proper maintenance and care yourfurnacewilloperateeconomically and dependably Basic maintenance which can easily be accomplished by someone who follows the directions is found on this and the following pages However before beginning maintenance follow the...

Page 6: ...nspect the gas burner see Fig 23 for dirt rust or scale Then inspect the inducer vent con nection area and the vent pipe for rust NOTE If dirt rust soot or scale accu mulations are found call your servic ing dealer DO NOT OPERATE THE FURNACE 3 Inspect the vent pipe for a sag holes or a disconnection A hori zontal vent pipe must slope upward away from the furnace If rusty joints or seams or signs o...

Page 7: ...NANCE In addition to the type of routine main tenance you might be willing to do your furnace should be inspected regularly by a properly trained service technician An annual inspection or biennial inspection at least should include the following 1 Inspection of all combustion prod uct passages including the burn ers heat exchanger inducer and vent pipe 2 Inspection of all combustion air and venti...

Page 8: ...TALLATION DATA Date Installed Dealer Name Address City State Zip Telephone FURNACE Product No Model No Serial No ACCESSORIES Product No Model No Serial No Product No Model No Serial No SPLIT SYSTEM OUTDOOR UNIT Product No Model No Serial No INDOOR COIL Product No Model No Serial No Product No Model No Serial No Product No Model No Serial No ...

Reviews: