Bryant Evolution Extreme 186CNV Service Manual Download Page 37

186CNV / 284ANV: Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

37

TXV Operation

The TXV is a metering device that is used in air conditioning and heat
pump  systems  to  adjust  to  changing  load  conditions  by  maintaining  a

preset  superheat  temperature  at  the  outlet  of  the  evaporator  coil.  The
volume of refrigerant metered through the valve seat is dependent upon
the following: 

1. Superheat  temperature  is  sensed  by  cap  tube  sensing  bulb  on

suction  tube  at  outlet  of  evaporator  coil.  This  temperature  is
converted  into  pressure  by  refrigerant  in  the  bulb  pushing
downward  on  the  diaphragm  which  opens  the  valve  via  the  push

rods.

2. The  suction  pressure  at  the  outlet  of  the  evaporator  coil  is

transferred  via  the  external  equalizer  tube  to  the  underside  of  the
diaphragm.  This is needed to account for the indoor coil pressure
drop.  Residential coils typically have a high pressure drop, which

requires this valve feature.

3. The pin is spring loaded, which exerts pressure on the underside of

the  diaphragm.  Therefore,  the  bulb  pressure  works  against  the
spring pressure and evaporator suction pressure to open the valve. 

If the load increases, the temperature increases at the bulb, which
increases the pressure on the top side of the diaphragm. This opens
the  valve  and  increases  the  flow  of  refrigerant.  The  increased

refrigerant  flow  causes  the  leaving  evaporator  temperature  to
decrease.  This lowers the pressure on the diaphragm and closes the
pin. The refrigerant flow is effectively stabilized to the load demand

with negligible change in superheat.

Accumulator

The accumulator is specifically designed to operate with Puron® or R22
respectfully; use only factory-authorized components. Under some light
load conditions  on  indoor coils,  liquid  refrigerant is present in suction
gas returning to compressor. The accumulator stores liquid and allows it
to boil off into a vapor so it can be safely returned to compressor. Since a
compressor  is  designed  to  pump  refrigerant  in  its  gaseous  state,
introduction of liquid into it could cause severe damage or total failure of
compressor.
The  accumulator  is  a  passive  device  which  seldom  needs  replacing.
Occasionally  its  internal  oil  return  orifice  or  bleed  hole  may  become
plugged. Some oil is contained in refrigerant returning to compressor. It
cannot boil off in accumulator with liquid refrigerant.  The bleed hole
allows a small amount of oil and refrigerant to enter the return line where
velocity of refrigerant returns it to compressor. If bleed hole plugs, oil is
trapped in accumulator, and compressor will eventually fail from lack of
lubrication. If bleed hole is plugged, accumulator must be changed. The
accumulator has a fusible element located in the bottom end bell. (See

Fig. 37

.)  This fusible element will melt at 430°F//221°C and vent the

refrigerant if this temperature is reached either internal or external to the
system.  If fuse melts, the accumulator must be replaced.
To change accumulator:

1. Shut off all power to unit.
2. Recover all refrigerant from system.
3. Break vacuum with dry nitrogen. Do not exceed 5 psig.

NOTE: 

Coil  may  be  removed  for  access  to  accumulator.  Refer  to

appropriate sections of Service Manual for instructions.

4. Remove accumulator from system with tubing cutter.
5. Tape ends of open tubing.

6. Scratch  matching  marks  on  tubing  studs  and  old  accumulator.

Scratch matching marks on new accumulator. Unbraze stubs from
old accumulator and braze into new accumulator.

7. Thoroughly  rinse  any  flux  residue  from  joints  and  paint  with

corrosion-resistant coating such as zinc-rich paint.

8. Install factory authorized accumulator into system with copper slip

couplings.

9. Evacuate and charge system.

Pour  and  measure  oil  quantity  (if  any)  from  old  accumulator.  If  more
than 20 percent of oil charge is trapped in accumulator, add new PVE oil
to compressor to make up for this loss. 

A88410

Fig. 37 – Accumulator

Vapor Injection Operation (5 Ton Models)

Some 284ANV and 186CNV models contain an additional refrigeration
circuit known as a vapor injection circuit. When active this circuit will

increase  the  capacity  of  the  outdoor  unit  with  a  minimal  increase  in
power consumption. The result is higher capacity at a higher efficiency.
This circuit is only active at extreme heating and cooling temperatures

and only in efficiency mode. 
The vapor injection circuit routes a portion of the subcooled liquid from
the  condenser  through  a  vapor  injection  EXV  (EXV-VI)  and  into  a
brazed-plate  heat  exchanger  (BPHX)  The  resulting  superheated  vapor

will  return  to  the  compressor  and  be  "injected"  into  the  mid  port.
Meanwhile subcooled liquid leaving the condenser is routed through the
other portion of the BPHX and is further subcooled before exiting to the

evaporator section of system, thus improving the capacity.

A200183

Fig. 38 – Vapor Injection Operation

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
Wear  safety  glasses,  protective  clothing,  and  gloves  when  handling
refrigerant.

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.
Before  installing,  modifying,  or  servicing  system,  main  electrical
disconnect switch must be in the OFF position. There may be more than
1 disconnect switch. Lock out and tag switch with a suitable warning

label. 

430

°

 FUSE

ELEMENT

BPHX

EXV-VI

COMPRESSOR

MID-PORT

DISCHARGE PORT

SUCTION PORT

CONDENSER

HX

EVAPORATOR

EX VALVE

Summary of Contents for Evolution Extreme 186CNV

Page 1: ...nt Low Fan Speed 9 Fan Operating Exceptions 9 Cooling Control 9 Heating Control 9 Super Heat Control 9 Defrost Mode 9 Defrost Interval 10 Defrost Process 10 PCM Indicators and Display Operation 10 Sta...

Page 2: ...ves a Seasonal Energy Efficiency Ratio SEER of up to 24 and up to 13 Heating Seasonal Performance Factor HSPF and the AC achieves up to 26 SEER To ensure all of the above technology provides the ultim...

Page 3: ...not controlled relative to the phase of the power provided by the transformer in the indoor equipment Rh Wiring requirements in this manual do not connect Rc and Rh together For any non standard wiri...

Page 4: ...any time specifications and designs without notice and without obligations 4 Fig 2 Compressor Fan Sub System Diagram Fig 3 Wiring Diagram 186CNV 284ANV Model sizes 2 5 tons 208 230 1 FILTER REACTOR S...

Page 5: ...0 rpm to 800 rpm depending on air movement requirements The fan on board VFI will automatically limit fan speed if fan load current reaches operating limits Crankcase Heater Some equipment has a crank...

Page 6: ...sure that Rc and Rh are not connected together Doing so may result in destroying one or both of the transformers in this and the internal equipment PCM Indicators and Matrix Display The PCM contains t...

Page 7: ...he right to change at any time specifications and designs without notice and without obligations 7 A200049 A200044 Fig 7 PCM Control Board Bluetooth Service Port Status LED Yellow CCN Communication LE...

Page 8: ...alve for regulating refrigerant flow during heating operation The EXV H is driven by a 12VDC 2 phase uni polar stepper motor The EXV H has a 475 step range between fully closed and fully open The PCM...

Page 9: ...oor equipment and under charged or over charged systems Sump Heat When the compressor is not running the compressor sump may need to be heated to prevent liquid refrigerant from collecting in the sump...

Page 10: ...e Comm light is On then communication has been received within the last 2 minutes and the equipment is operating in normal communication mode If the Comm light is Off then communication has not been r...

Page 11: ...No code will be displayed if the most recent highest priority diagnostic code occurred more than 240 hours of equipment operating time before entering recall mode No code will be displayed if there ha...

Page 12: ...nd indoor fan for proper operation Low Pressure Protection The equipment monitors suction pressure relative to low pressure limits Low pressure limits are compressor speed and model dependent If the c...

Page 13: ...oil Temperature OCT Thermistor The OCT thermistor provides the coil liquid line temperature to the PCM where it is used primarily for defrost control The OCT thermistor is located on an extension tube...

Page 14: ...dentical Either pressure transducer can connected to either input The software in the PCM detects which transducer is connected to which input and assigns the signals accordingly Signals used by contr...

Page 15: ...s received by PCM If this fault is active inspect PCM to Bluetooth module harness and ensure both ends are fully seated on board header Also inspect and repair any wire damage on harness If no green o...

Page 16: ...This code will be set if fuse 2 is blown or missing on PCM board Fuse 2 only powers the LLS When this fault is active the system will not operate The code will clear once fuse is replaced with new un...

Page 17: ...connections wire damage and wire order This code indicates that the VFD is not able to rotate the compressor rotor enough to complete starting process indicating compressor damage or high pressure dif...

Page 18: ...equired from compressor and VFD The PEV will open 2 5 minutes after compressor shutdown if pressure differential is between 200 300psi or if pressure differential is greater than 50psi and demand is p...

Page 19: ...observed replace sensor If measured resistance is within allowable range replace PCM Code 54 02 ODT Shorted The discharge thermistor is used to protect the compressor and ensure discharge superheat i...

Page 20: ...will operate to a known position as the valve does not have the capability to feedback actual position The PCM software must know the starting point and then count when stepper motor is pulsed At the...

Page 21: ...ill be reduced to 0 If measurement is open replace reactor Otherwise replace VFD Code 81 14 VFD System Fault Unbalanced PFCM Code 81 54 VFD System Lockout Unbalance PFCM Applicable to 4 and 5 ton mode...

Page 22: ...resistance against table Listen to compressor during operating for abnormal noise indicating physical damage VFD may have internal damage causing high current or compressor may be damaged Code 83 57 V...

Page 23: ...with disconnect if malfunction persists replace VFD Code 88 32 VFD Internal Fault IPM Temp Sens The VFD has internal temperature sensors to monitor critical power components and take action if operati...

Page 24: ...ue to operate normally since the only way to correct this fault is to replace VFD Code 88 38 VFD Internal Fault DC Discharge Code 88 78 VFD Lockout Int DC Discharge The unit VFD converts boosts 230VAC...

Page 25: ...55 Compressor Low Discharge Limit 34 11 58 Compressor High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54...

Page 26: ...t Limit 1 Speed Reduction 12 Compressor Current Limit 2 Speed Reduction 15 55 Compressor Current Limit 3 Shutdown 16 56 Compressor Current Limit 4 Shutdown 57 Compressor Underspeed Shutdown 84 11 58 V...

Page 27: ...nd designs without notice and without obligations 27 A200187 Fig 18 2T 3T Control Box A200188 Fig 19 4T 5T Control Box Note 4T VFD similar not exact 5T reactors have additional chokes to meet FCC requ...

Page 28: ...otice and without obligations 28 A200191 Fig 22 2 3T VFD Connections VFD control relay and LED Fan motor connections VFD to PCM comm connection DC DC terminals Fan motor fuse Compressor UVW connection...

Page 29: ...192 Fig 23 4 5T VFD Connections Note 4T uses separate terminals VFD to PCM comm connection Fan motor connections Compressor UVW connections DC DC terminals Reactor connection Filter board input VFD co...

Page 30: ...186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 30 A200193 Fig 24 PCM used on all models...

Page 31: ...designs without notice and without obligations 31 A200194 Fig 25 Bluetooth Module used on all models A200195 Fig 26 Fan Motor used on all models A200196 Fig 27 2 3 4T Rector Note 4Tuses 2 reactors A2...

Page 32: ...rer reserves the right to change at any time specifications and designs without notice and without obligations 32 A200199 Fig 30 PCM to Bluetooth Module Comm Cable used on all models A200200 Fig 31 VF...

Page 33: ...186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 33 A200201 Fig 32 PCM Wiring Diagram...

Page 34: ...brazing alloy is used on copper to brass copper to steel or copper to copper Flux is required when using silver brazing alloy Do not use low temperature solder 3 Fluxes should be used carefully Avoid...

Page 35: ...flow of refrigerant in system This reversing valve device is easy to troubleshoot and replace The reversing valve solenoid can be checked with power off with an ohmmeter Check for continuity and shor...

Page 36: ...where acid might occur such as burnout Heat pump units must have the drier installed between the compressor and accumulator only Remove after 10 hours of operation Never leave suction line filter drie...

Page 37: ...l eventually fail from lack of lubrication If bleed hole is plugged accumulator must be changed The accumulator has a fusible element located in the bottom end bell See Fig 37 This fusible element wil...

Page 38: ...igerant is leaking at that point A simple and inexpensive method of testing for leaks is to use soap bubbles See Fig 40 Any solution of water and soap may be used Soap solution is applied to all joint...

Page 39: ...ngthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center with your HVACpartners credentials at www mlctraining...

Page 40: ...Company Edition Date 06 20 Catalog No SM186CNV 284ANV 01 Replaces NEW 186CNV 284ANV Service Manual Manufacturer reserves the right to change at any time specifications and designs without notice and...

Reviews: