background image

5

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate

triple evacuation method may be used. See Service Manual for
triple evacuation method.

Always break a vacuum with dry

nitrogen.

_

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of

accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and
liquid water. (See Fig. 4)

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS

2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 4 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Do not supply power to unit with compressor terminal

box cover removed.

Be sure field wiring complies with local and national fire, safety,

and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit

control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault

should occur. The ground may consist of electrical wire or

metal conduit when installed in accordance with existing

electrical codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT

PER N. E. C. AND/OR

LOCAL CODES

CONTACTOR

GROUND LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

A91056

Fig. 5 -- Line Power Connections

Connect Control Wiring

Route low--voltage control wires through control wiring grommet
and connect leads to control board.
For Evolution, connect to ABCD only.

For standard

non--communicating thermostats, connect to standard thermostat

connections R, C, Y1 and Y2.
Use No. 18 AWG color--coded, insulated (35

_

C minimum) wire

for all installations.
All wiring must be NEC Class 1 and must be separated from
incoming power leads.
Use furnace transformer or fan coil transformer for control power,

24--v/40--va minimum. The outdoor unit requires a minimum of
27va/24 vac control power.

Final Wiring Checks

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

Furnish power to crankcase heater a minimum of 24 hr before

starting unit. To furnish power to heater only, set thermostat to
OFF and close electrical disconnect to outdoor unit.

NOTE

: On 187A models, starting the compressor without a

minimum of 12 hours of crankcase heat prior to initial start--up
may result in a compressor chattering noise and possible damage to
the compressor.

Install Accessories

Refer to the individual instructions packaged with kits or

accessories when installing.

180A

/187A

Summary of Contents for Evolution 180A

Page 1: ...gnize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words...

Page 2: ...tion Specifications for this unit in residential new construction market require the outdoor unit indoor unit refrigerant tubing sets metering device and filter drier listed in presale literature Ther...

Page 3: ...tubing diameters Refer to Table 2 for accessory requirements There are no buried line applications greater than 36 in 914 4 mm If refrigerant tubes or indoor coil are exposed to atmosphere they must...

Page 4: ...NIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Installation of filter drier in liquid line is required Refer to Fig 3 and install filter drier as...

Page 5: ...nit per Section 440 14 of NEC Route Ground and Power Wires Remove access panel to gain access to unit wiring Extend wires from disconnect through power wiring hole provided and into unit control box W...

Page 6: ...ard that allows the installing technician to select proper airflows For adjustments to control board and recommended A C SIZE and CFM ADJUST selections This fan coil has an adjustable blower off delay...

Page 7: ...n the outdoor board see Fig 6 indicates successful communication with the other system products The green LED will remain OFF until communications is established Once a valid command is received the g...

Page 8: ...ble 3 Outdoor Fan Motor PWM Outdoor Temp DC volts Tolerance 2 MODEL LOW STAGE OAT 104_F 40_C HIGH STAGE OAT 104_F 40_C LOW HIGH STAGE OAT 104_F 40_C 180A024 9 57 10 88 11 90 180A036 9 06 10 23 11 90 1...

Page 9: ...rd for the unit to operate NOTE The model plug takes priority over factory model information input at the factory If the model plug is removed after initial power up the unit will operate according to...

Page 10: ...ontactor Open 187A models No 230V at Compressor 180A models If the compressor voltage is not sensed when the compressor should be starting the appropriate contactor may be stuck open or there is a wir...

Page 11: ...ed to motor windings Compressor Control Contactors The contactor s have a 24 volt coil The electronic control board controls the operation of the appropriate contactors TEMPERATURE THERMISTORS Thermis...

Page 12: ...at all wiring and tubing is secure in unit before adding panels and covers Securely fasten all panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Users Manual w...

Page 13: ...demand exists Possible causes are internal compressor overload trip or start relay and capacitor held in circuit too long if installed high stage Ther mal Cutout 72 Compressor operation detected then...

Page 14: ...OM C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Indicates connection may not be required available A08060 Edg...

Page 15: ...with POE oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave Puron suction line filter driers i...

Page 16: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date...

Reviews: