6
ERVXXLHB1200, HRVXXLHB1150, HRVXXLHB1250 (cont.)
HVI RATED ENERGY PERFORMANCE
MODEL
MODE
SUPPLY
TEMP
NET AIR
FLOW
POWER
CONSUMED
(WATTS)
SENSIBLE
RECOVERY
EFFICIENCY
APPARENT
SENSIBLE
EFFECTIVE-
NESS
LATENT
RECOVERY
MOISTURE
TRANSFER
TOTAL
RECOVERY
EFFICIENCY
_
C
_
F
L/S CFM
ERVXXLHB1200
Heat
0
32
39
80
84
60
72
0.60
0
32
54
114
113
58
69
0.53
0
32
79
167
169
56
66
0.45
---25
---13
31
65
116
41
86
0.47
Cool
35
95
39
82
81
52
HRVXXLHB1150
Heat
0
32
31
66
67
67
79
0
0
32
40
86
74
65
75
0
0
32
54
115
90
61
70
0
---25
---13
38
81
87
60
76
0.02
Cool
35
95
HRVXXLHB1250
Heat
0
32
39
82
71
65
75
0.01
0
32
61
130
129
60
69
0.01
---25
---13
40
84
114
60
76
0.03
Cool
35
95
VENTILATION PERFORMANCE
MODEL
EXT. STATIC
PRESSURE
NET SUPPLY AIR
FLOW
GROSS AIR FLOW
SUPPLY
EXHAUST
Pa
In w.g.
L/S
CFM
L/S
CFM
L/S
CFM
ERVXXLHB1200
25
0.1
105
222
106
225
106
225
75
0.3
93
198
94
200
100
212
100
0.4
86
183
88
186
93
198
150
0.6
70
148
71
150
75
158
200
0.8
50
107
51
108
29
61
HRVXXLHB1150
25
0.1
85
180
86
182
92
194
75
0.3
77
163
77
164
81
171
100
0.4
71
150
71
151
71
151
150
0.6
60
128
61
130
40
85
175
0.7
51
108
52
110
27
57
HRVXXLHB1250
25
0.1
106
225
107
227
118
249
75
0.3
96
204
97
205
111
235
100
0.4
90
192
91
193
107
226
150
0.6
76
161
76
162
89
189
175
0.7
67
142
67
143
75
159
NOTE
:
For additional data points, refer to HVI Directory at www.hvi.org