Bryant ELECTRIC AIR CONDITIONER 561C User Manual Download Page 7

 

—7—

 

* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.
If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.

** Time-delay fuse or circuit breaker.

†† Start assist capacitor and relay required when using liquid solenoid valve or hard shutoff TXV (except 036 and 042, Series A; 048 and 060, Series A/B 

single phase; and all 3-phase units). Do not use hard shutoff TXV with liquid solenoid valve.

‡‡ Use with low-ambient controller.

*** Fan motor with ball bearings required.

N/A—Not Applicable

 

NOTES:

 

1. All motors/compressors contain internal overload protection.
2. Copper wire must be used from service disconnect to unit.
3. Control circuit is 24v on all units and requires external power source.

 

ACCESSORY USAGE GUIDELINE

 

* For tubing line sets between 50 and 175 ft, refer to Residential’s Split Systems Long-Line Application Guidelines.

† Only when low-pressure switch is used.

 

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

 

1. Ball Bearing Fan Motor

 

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

SUGGESTED USE:  Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

 

2. Coastal Filter

 

 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. 

SUGGESTED USE:  In geographic areas where salt damage could occur.

 

3. Compressor Start Assist—Capacitor/Relay Type

 

 

Start capacitor and start relay which gives ‘‘hard’’ boost to compressor motor at each start-up. 

SUGGESTED USE:  Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.

 

4. Compressor Start Assist—PTC Type

 

 

Solid-state electrical device which gives a ‘‘soft’’ boost to compressor motor at each start-up. 

SUGGESTED USE:  Installations with marginal power supply.

Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.

 

5. Crankcase Heater

 

 

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication 
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. 

SUGGESTED USE:  When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Controller.)
All commercial installations.

 

6. Cycle Protector

 

 

Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has 
been interrupted for any reason, including normal room thermostat cycling. 

SUGGESTED USE:  Installations in areas where power interruptions are frequent.

Where user is likely to ‘‘play’’ with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.

 

7. Evaporator Freeze Thermostat

 

 

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. 

SUGGESTED USE:  All units where Winter Start Control has been added.

 

8. Filter Drier

 

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.

SUGGESTED USE:  All split-system units.

 

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

 

Crankcase Heater

Yes

Yes

No

Evaporator Freeze Thermostat

Yes

No

No

Winter Start Control

Yes†

No

No

Accumulator

No

No

No

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

Low Ambient Controller

or

MotorMaster® Control

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes

No

No

Summary of Contents for ELECTRIC AIR CONDITIONER 561C

Page 1: ...each unit with a hard smooth finish that will last for many years All screws on cabinet exterior are coated for a long lasting rust resistant quality appearance TOTALLY ENCLOSED FAN MOTOR Means greate...

Page 2: ...17 3 4 7 7 8 8 3 8 9 3 8 18 X 18 024 A D 18 23 15 16 3 3 16 5 8 3 15 16 5 16 17 3 4 10 3 16 16 1 8 17 3 4 7 7 8 8 3 8 9 1 2 18 X 18 030 A D 22 1 2 21 15 16 3 3 16 3 4 3 11 16 18 1 8 19 3 4 22 1 4 14 3...

Page 3: ...1 0 66 5 59 5 018 D 80 57 5 64 0 69 5 72 0 71 5 68 0 60 0 024 A 80 59 5 65 0 69 5 74 0 73 0 70 0 62 0 024 D 82 55 5 63 0 68 0 71 0 70 5 67 5 58 5 030 A 80 55 0 62 5 73 5 74 0 71 0 67 5 59 5 030 D 80 5...

Page 4: ...AL EQUIPMENT Coastal Filter KAACF0601SML KAACF0401MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Low Ambient Controller N A P251 0083 RCD Crankcase Heater KAACH1001AAA Inlet Grille Kit...

Page 5: ...nd 1125 1100 1125 1 5 and 1125 1 4 and 1125 1 5 and 1125 1 4 and 1125 Volts Hertz Phase 208 230 60 1 460 60 1 208 230 60 1 460 60 1 Condenser Airflow CFM 2500 3400 OPTIONAL EQUIPMENT Coastal Filter KA...

Page 6: ...Volts Hertz Phase 208 230 60 1 460 60 1 208 230 60 1 460 60 1 Condenser Airflow CFM 3400 OPTIONAL EQUIPMENT Coastal Filter KAACF0501LRG Time Delay Relay KAATD0101TDR Cycle Protector Standard KSACY0101...

Page 7: ...ations where outdoor design temperature exceeds 105 F 40 6 C Replacement installations with hard shutoff expansion valve on indoor coil Installations where Liquid Line Solenoid Valve has been added 4...

Page 8: ...nt pressure drops to about 27 psig Prevents indoor coil freeze up due to loss of indoor airflow Provides protection against compressor damage due to loss of refrigerant charge To prevent rapid compres...

Page 9: ...10 00 9 05 CC5A CD5AW030 22 600 NONE 10 00 10 00 9 10 CE3AA024 22 600 NONE 10 00 10 00 9 10 CE3AA030 23 000 NONE 10 20 10 20 9 20 CF5AA024 22 600 NONE 10 00 10 00 9 10 CK3BA024 22 400 NONE 10 00 10 00...

Page 10: ...5BT036 29 000 TDR 11 00 11 00 10 05 CK5A CK5BW030 28 000 TDR 10 50 10 50 9 70 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CC5A CD5AW030 28 000 TDR 10 50 10 50 9 80 CD5AW036 29 000 TDR 11 00 11 00 10...

Page 11: ...R 10 50 10 50 9 80 COILS 333 B J AV060100 VARIABLE SPEED FURNACE CC5A CD5AA042 33 400 TDR 10 80 10 80 10 05 CD5AW036 33 400 TDR 10 50 10 50 10 00 CK5A CK5BA042 33 400 TDR 10 80 10 80 10 10 CK5A CK5BT0...

Page 12: ...42 40 000 TDR 10 50 10 50 9 45 CC5A CD5AC048 40 000 TDR 10 70 10 70 9 45 CC5A CD5AW042 40 000 TDR 10 50 10 50 9 55 CC5A CD5AW048 40 000 TDR 10 70 10 70 9 45 CD5AA048 40 000 TDR 10 70 10 70 9 45 CE3AA0...

Page 13: ...0 TDR TXV 11 00 9 55 FC4BNB070 48 500 TDR TXV 11 00 9 50 FG3AA048 46 000 NONE 10 00 10 50 10 50 9 20 FG3AA060 47 000 NONE 10 20 10 50 10 50 9 35 FK4CNF005 48 000 TDR TXV 11 50 9 90 FK4CNF006 49 000 TD...

Page 14: ...060100 VARIABLE SPEED FURNACE CC5A CD5AA060 46 000 TDR 10 50 10 50 9 15 CC5A CD5AC048 45 500 TDR 10 80 10 80 9 30 CK3BA048 45 500 TDR 10 80 10 80 9 30 CK3BA060 45 500 TDR 11 00 11 00 9 15 CK5A CK5BA04...

Page 15: ...8 15 8 1 77 14 9 14 9 1 87 14 1 14 1 1 96 13 2 13 2 2 05 12 3 12 3 2 14 675 72 21 9 10 8 1 86 20 7 10 4 1 97 19 4 9 86 2 07 18 0 9 39 2 18 16 7 8 90 2 27 15 3 8 44 2 36 67 19 9 13 7 1 80 18 7 13 2 1 9...

Page 16: ...91 20 0 11 4 3 00 67 25 8 18 3 2 37 24 3 17 7 2 48 22 7 17 1 2 59 21 2 16 5 2 69 19 6 15 8 2 79 18 0 15 2 2 87 62 23 4 22 0 2 28 22 0 21 3 2 39 20 6 20 4 2 50 19 3 19 3 2 60 18 1 18 1 2 70 16 9 16 9...

Page 17: ...rmance With Other Indoor Sections Indoor Section Unit Size Cooling Indoor Section Unit Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 04 1 01 COILS 333 B J AV048080 VARIABLE SPEED FURNACE...

Page 18: ...0 1 00 COILS 333 B J AV060100 VARIABLE SPEED FURNACE 042 1 00 1 00 CC5A CD5AA 042 0 99 0 92 CC5A CD5AW 042 1 00 1 00 CD5AW 036 0 99 0 92 CD5AW 036 1 00 1 00 CK5A CK5BA 042 0 99 0 92 CE3AA 036 0 99 1 0...

Page 19: ...2 26 6 3 56 34 0 25 7 3 74 31 8 24 8 3 93 29 6 23 9 4 11 27 3 23 1 4 29 62 34 9 33 1 3 24 33 0 32 0 3 42 31 0 30 8 3 61 29 2 29 2 3 80 27 5 27 5 3 99 25 8 25 8 4 19 57 34 1 34 1 3 22 32 5 32 5 3 41 30...

Page 20: ...Unit Size Cooling Indoor Section Unit Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 00 CD5AA 048 1 00 0 93 CC5A CD5AC 048 0 99 1 00 CE3AA 042 1 00 0 94 CC5A CD5AW 042 1 00 1 00 048...

Page 21: ...0 4 97 31 8 25 8 5 17 62 41 1 37 5 3 88 38 7 36 3 4 11 36 3 35 0 4 35 34 0 33 6 4 57 31 7 31 7 4 78 29 3 29 3 5 01 57 39 4 39 4 3 82 37 6 37 6 4 07 35 7 35 7 4 31 33 7 33 7 4 55 31 7 31 7 4 78 29 3 2...

Page 22: ...or Section Unit Size Cooling Capacity Power Capacity Power CD5AA 048 1 00 1 00 CD5AA 048 0 99 1 00 CC5A CD5AA 060 1 00 1 00 CD5AC 048 0 99 1 00 CC5A CD5AC 048 0 98 0 99 CE3AA 048 0 99 1 01 CC5A CD5AW...

Page 23: ...44 0 40 7 4 55 41 9 39 6 5 05 39 8 38 4 5 60 37 5 37 0 6 18 35 2 35 2 6 79 57 44 1 44 1 4 04 42 5 42 5 4 52 40 8 40 8 5 03 39 1 39 1 5 57 37 2 37 2 6 17 35 2 35 2 6 79 1800 72 56 2 28 4 4 37 53 7 27...

Page 24: ...5 17 64 0 31 3 5 67 61 2 30 3 6 23 58 3 29 2 6 85 55 2 28 1 7 53 51 9 26 9 8 27 67 60 8 40 4 4 99 58 4 39 4 5 48 55 8 38 3 6 04 53 1 37 2 6 65 50 2 36 0 7 33 47 2 34 8 8 05 62 55 5 48 4 4 83 53 2 47...

Page 25: ...9 0 139 0 149 0 55 TCG 35 8 33 8 31 8 29 6 27 3 25 1 23 0 20 9 KW 2 13 2 29 2 45 2 60 2 74 2 87 2 98 3 07 SDT 70 9 83 8 97 0 109 0 120 0 131 0 141 0 151 0 561C030 A D 30 TCG 28 0 26 0 24 0 22 0 20 1 1...

Page 26: ...CG 46 6 44 7 42 7 40 6 38 4 36 1 33 8 31 4 KW 3 28 3 61 3 99 4 41 4 87 5 37 5 89 6 44 SDT 77 7 88 2 98 6 109 0 119 0 129 0 139 0 149 0 40 TCG 50 9 48 8 46 7 44 4 42 1 39 7 37 2 34 7 KW 3 34 3 68 4 06...

Page 27: ...50 ft indoor coil below 150 ft 6 For interconnecting refrigerant tube lengths between 50 and 175 ft consult Residential Split Systems Long Line Application Guideline available from equipment distribut...

Page 28: ...cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Ai...

Reviews: