Table 12 — Accessory/FIOP Static Pressure (in. wg)
LEGEND
*Do not operate unit with electric heat at this cfm. Operation at this cfm
is below electric heat required minimum cfm.
†Do not operate unit at this cfm. Operation at this cfm is above unit
maximum cfm limit.
NOTES:
1. Heaters are rated at 208 v, 240 v and 480 v.
2. The factory assembled horizontal adapter substantially improves
fan performance. See Fig. 30.
3. The static pressure must be added to external static pressure. The
sum and the indoor-air section entering-air cfm should then be
used in conjunction with the Fan Performance table to determine
blower rpm, bhp, and watts.
Table 13 — Fan Rpm at Motor Pulley Settings* (Factory-Supplied Drives)
*Approximate fan rpm shown.
†Due to belt and pulley size, pulley cannot be set to this number of turns
open.
NOTE: To run units at speeds not listed, field-supplied drives are
required.
Table 14 — Indoor-Fan Motor Performance
LEGEND
*Extensive motor and electrical testing on these units ensures that the
full horsepower range of the motors can be utilized with confidence.
Using fan motors up to the horsepower ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
ACCESSORY/FIOP
UNIT SIZE
542J
UNIT VOLTAGE
kW
AIRFLOW (Cfm)
3750
4000
4500
5000
5600
6000
6250
7200
7500
Electric Heaters
150
208/230-3-60
14,34
42,56
0.05
0.06
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.10
0.09
0.12
0.09
0.13
†
†
460-3-60
15,32
55
0.05
0.06
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.10
0.09
0.12
0.09
0.13
†
†
180
208/230-3-60
26,34
42,56
*
*
*
*
0.08
0.10
0.09
0.12
0.09
0.13
0.11
0.16
0.12
0.17
460-3-60
32
55
*
*
*
*
0.08
0.10
0.09
0.12
0.09
0.13
0.11
0.15
0.12
0.17
EconoMi$erIV
All
All
—
0.03
0.03
0.04
0.05
0.06
0.07
0.07
0.09
0.10
Glycol Coil
All
All
—
0.16
0.18
0.22
0.26
0.31
0.35
0.37
0.44
0.46
FIOP — Factory-Installed Option
UNIT 542J
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
150
†
†
1132
1105
1078
1051
1024
997
970
943
916
889
862
180
†
†
1010
989
968
947
926
905
883
862
841
820
799
UNIT
542J
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
MOTOR
EFFICIENCY
150
208/230
4.25
3775
10.5
85.8
460
4.9
85.8
180
208/230
5.90
5180
15.8
87.5
460
7.9
87.5
Bhp —
Brake Horsepower
NOTE: The CRRFCURB013A00 horizontal supply and return adapter
accessory improves 542J fan performance by increasing external static
pressure by amount shown above.
Fig. 30 — Horizontal Supply/Return Fan Performance
with CRRFCURB013A00 Horizontal Supply Adapter
Fig. 31 — Fan Performance Using Accessory
Power Exhaust
Summary of Contents for DURAPAC PLUS SERIES 542J
Page 27: ... 27 Fig 40 Typical Wiring Diagram 542J150 208 230 3 60 V Shown ...
Page 28: ... 28 Fig 41 Typical Component Arrangement 542J150 208 230 3 60 V Shown ...
Page 33: ... 33 Fig 44 Troubleshooting Chart Heating Cycle ODT Outdoor Temperature ...
Page 34: ... 34 Fig 45 Troubleshooting Chart Cooling Cycle ...
Page 38: ...Copyright 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 5354 203 ...
Page 39: ......