Page 104
SECTION 4.4
DIAGNOSTIC TESTS
PART 4
DC CONTROL
4. A starter motor in good condition will be within the
following specifications:
Single Cylinder
V-twin
Minimum rpm
800
4500
Maximum Amps
9
50
Figure 15. Testing Starter Motor Performance
TEST 51 - CHECK FUEL SUPPLY AND
PRESSURE
DISCUSSION:
The air-cooled prepackaged generator was factory
tested and adjusted using natural gas as a fuel. If
desired, LP (propane) gas may be used. However,
when changing over to propane, some minor
adjustments are required. The following facts apply:
• An adequate gas supply and sufficient fuel pressure
must be available or the engine will not start.
• Minimum recommended gaseous fuel pressure at
the generator fuel inlet connection is 11 inches
water column (6.38 ounces per square inch).
• Maximum gaseous fuel pressure at the generator
fuel inlet connection is 14 inches water column (8
ounces per square inch).
• When propane gas is used, only a "vapor
withdrawal" system may be used. "This type of
system utilizes the gas that form above the liquid
fuel the vapor pressure must be high enough
engine operation.
• The gaseous fuel system must be properly tested
for leaks following installation and periodically
thereafter. No leakage is permitted. Leak test
methods must comply strictly with gas codes.
DANGER: GASEOUS FUELS ARE HIGHLY
EXPLOSIVE. DO NOT USE FLAME OR HEAT
TO TEST THE FUEL SYSTEM FOR LEAKS.
NATURAL GAS IS LIGHTER THAN AIR,
TENDS TO SETTLE IN HIGH PLACES. LP
(PROPANE) GAS IS HEAVIER THAN AIR,
TENDS TO SETTLE IN LOW AREAS. EVEN
THE SLIGHTEST SPARK CAN IGNITE THESE
GASES AND CAUSE AN EXPLOSION.
PROCEDURE:
A water manometer or a gauge that is calibrated in
"ounces per square inch" may be used to measure
the fuel pressure. Fuel pressure at the inlet side of the
fuel solenoid valve should be between 11 - 14 inches
water column as measured with a manometer, or
6.38-8.00 ounces per square inch as measure with a
pressure gauge.
The fuel pressure can be checked using a pressure
tester kit (Generac p/n 0C7977). See Figure 16 for
the gas pressure test point on the fuel regulator.
NOTE: Where a primary regulator is used to
establish fuel inlet pressure, adjustment of that
regulator is usually the responsibility of the fuel
supplier or the fuel supply system installer.
RESULTS:
1. If fuel supply and pressure are adequate, but engine will
not start, go on to Test 53.
2. If generator starts but runs rough or lacks power, repeat
the above procedure with the generator running and
under load. The fuel system must be able to maintain
11”-14” water column at all load requirements. If proper
fuel supply and pressure is maintained, go to Test 55.
Figure 16. Air Cooled Engine Fuel System
Summary of Contents for ASPAS1BBA007
Page 4: ...Page 4 SPECIFICATIONS MOUNTING DIMENSIONS...
Page 5: ...Page 5 SPECIFICATIONS MOUNTING DIMENSIONS...
Page 24: ...Page 24 NOTES PART 1 GENERAL INFORMATION...
Page 32: ...Page 32 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS PART 2 AC GENERATORS...
Page 33: ...Page 33 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS AC GENERATORS PART 2...
Page 34: ...Page 34 SECTION 2 3 TROUBLESHOOTING FLOWCHARTS PART 2 AC GENERATORS...
Page 60: ...Page 60 SECTION 3 3 TROUBLESHOOTING FLOW CHARTS PART 3 V TYPE PREPACKAGED TRANSFER SWITCHES...
Page 70: ...Page 70 SECTION 3 4 DIAGNOSTIC TESTS PART 3 V TYPE PREPACKAGED TRANSFER SWITCHES...
Page 90: ...Page 90 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Page 91: ...Page 91 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Page 92: ...Page 92 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Page 93: ...Page 93 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Page 94: ...Page 94 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS PART 4 DC CONTROL...
Page 95: ...Page 95 SECTION 4 3 TROUBLESHOOTING FLOW CHARTS DC CONTROL PART 4...
Page 138: ...PART 7 ELECTRICAL DATA WIRING DIAGRAM 8 CIRCUIT LOAD CENTER Page 138 DRAWING 0E7687A...
Page 140: ...Page 140 DRAWING 07687 PART 7 ELECTRICAL DATA WIRING DIAGRAM 10 12 CIRCUIT LOAD CENTER...
Page 142: ...Page 142 PART 7 ELECTRICAL DATA NOTES...
Page 144: ...Part No 0F4676 Revision 02 25 05 Printed in U S A Catalog No DMASPAS 07 1...