
987MB: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
15
A11038
Fig. 22 – Horizontal Return Air Configurations
and Restrictions
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove this panel when bottom return air is used.
This panel may be used as the bottom closure of an accessory bottom
return air box, or discarded. To remove bottom closure panel, see
.
A170123
Fig. 23 – Removing Bottom Closure Panel (2 Screws)
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. This panel MUST be in place when only side return
air is used. Where required by code, seal bottom closure to furnace with
tape, mastic or other durable sealing method.
NOTE:
Side return-air openings can be used in UPFLOW and some
HORIZONTAL configurations. Do not use side return-air openings in
DOWNFLOW configuration, see
,
.
Downflow Installation
NOTE:
The furnace must be pitched as shown in
for proper
condensate drainage.
Supply Air Connections
NOTE:
For downflow applications, this furnace is approved for use on
combustible flooring when any one of the following 3 accessories are
used:
• Manufacturer’s downflow combustible floor subbase
• Manufacturer’s cased evaporator coil
• Manufacturer’s evaporator coil casing
1. Determine application being installed from
2. Construct hole in floor per
.
3. Construct plenum to dimensions specified in
and
4. If downflow subbase is used, install as shown. If manufacturer’s
cased evaporator coil or coil casing is used, install as shown in
NOTE:
It is recommended that the perforated supply-air duct flanges be
completely removed from furnace when installing the furnace on a
factory-supplied cased coil or coil box. To remove the supply-air duct
flange, use wide duct pliers or hand seamers to bend flange back and
forth until it breaks off. Be careful of sharp edges, see
.
The return-air duct must be connected to return-air opening (bottom
inlet). DO NOT cut into casing sides (left or right). Bypass humidifier
connections should be made at ductwork or coil casing sides exterior to
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in bottom
return-air opening. Remove and discard this panel when bottom return
air is used in downflow applications. To remove bottom closure panel,
.
Horizontal Installation
NOTE:
The furnace must be pitched forward as shown in
for
proper condensate drainage.
WARNING
!
FIRE AND PROPERTY HAZARD
Failure to follow this warning could result in equipment damage,
personal injury, or property damage.
When furnace is installed in a downflow application, make sure water
lines and other sources of water cannot drip or fail in such a way that
water can collect on the blower motor, wiring, and furnace control
board.
HORIZONTAL TOP
RETURN NOT
PERMITTED FOR
ANY MODEL
WARNING
!
FIRE, EXPLOSION, AND CARBON MONOXIDE
POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not install the furnace on its back or hang furnace with control
compartment facing downward. Safety control operation will be
adversely affected. Never connect return-air ducts to the back of the
furnace.
CAUTION
!
MINOR PROPERTY HAZARD
Failure to follow this caution may result in minor property damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic
application or over a finished ceiling.