935SA: Installation, Start-up, Operating and Service Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
The HUM 24 VAC terminal is energized when the blower starts
during a call for heat. (See
NOTE:
DO NOT connect furnace control HUM 115 VAC terminal or
HUM 24 VAC terminal to H (humidifier) terminal on humidity sensing
thermostat, or similar device. See humidity sensing thermostat,
thermostat, or controller manufacturer’s instructions for proper
connection.
NOTE:
Use AWG No. 18 color-coded copper thermostat wire for
lengths up to 100 ft. (31 M). For wire lengths over 100 ft., use AWG No.
16 wire.
The 24-v circuit contains an automotive-type, 3-amp. fuse located on the
control. Any direct shorts during installation, service, or maintenance
could cause this fuse to blow. If fuse replacement is required, use ONLY
a 3-amp. fuse of identical size (see
).
Alternate Power Supplies
This furnace is designed to operate on utility generated power which has
a smooth sinusoidal waveform. If the furnace is to be operated on a
generator or other alternate power supply, the alternate power supply
must produce a smooth sinusoidal waveform for compatibility with the
furnace electronics. The alternate power supply must generate the same
voltage, phase, and frequency (Hz) (
) or the furnace rating plate.
Power from an alternate power supply that
is non-sinusoidal may
damage the furnace electronics
or cause erratic operation.
Contact the alternate power supply manufacturer for specifications and
details.
A190079
Fig. 40 – Typical Single-Stage Wiring Diagram
A190409
Fig. 41 – Example of Single Stage Furnace Control
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
COM
W
C
R
G
Y
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES:
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.
24-V THERMOSTAT
TERMINALS
PL2
–
(115-VAC) HOT SURFACE IGNITER &
INDUCER MOTOR CONNECTOR
(L2) NEUTRAL
CONNECTIONS
115-VAC (BL) BLOWER MOTOR LINE
VOLTAGE CONNECTION
EAC-1 TERMINAL
(115-VAC EAC + HUM 1.0 AMP MAX.)
PL1
–
LOW VOLTAGE MAIN HARNESS
CONNECTOR plus INDUCER PWM
TRANSFORMER 24-VAC
CONNECTIONS
3-AMP FUSE
STATUS LED LIGHT
HEAT OFF-DELAY
MODEL PLUG
CONNECTOR
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
BOARD PART NUMBER
LOCATION
COOLING SPEED
TAP
HEATING SPEED
TAP
PR
115-VAC (PR) TRANSFORMER
PRIMARY
J2 DEFEAT
JUMPER
TEST/TWIN
J2
J1
J1 HEAT OFF-DELAY
JUMPER SELECT
L1
HUM 115-VAC TERMINAL
(115-VAC EAC + HUM 1.0 AMP MAX.)
FACTORY RUN TEST PORT
(FACTORY ONLY)
PROGRAMMING FLASH PORTS
(FACTORY ONLY)
BL
115-VAC (L1) LINE VOLTAGE
CONNECTION
FAN SPEED TAP
PL3 - PRESSURE
TRANSDUCER INPUT
PL4
HUM
115VAC
SPARE UNUSED
TAPS