935SA: Installation, Start-up, Operating and Service Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
INSTALLATION
Preparing the Furnace – Before Setting in Place
1. Remove appropriate knockout based off the installation orientation.
L12F019B
Fig. 12 – Knockout Removal
2. Remove two of the factory-installed drain plugs from collector box.
Orientation specific drain plugs (see
).
3. Check that all pre-installed gaskets on trap components are present,
adhered, and undamaged.
A200075
Fig. 13 – Drain Plugs
A200076
Fig. 14 – Upflow Example of Trap Adapter Installation
A200064
Fig. 15 – Upflow Condensate Drain
A200065
Fig. 16 – Upflow - Offset of Condensate Drain
NOTICE
!
Upflow installations utilizing the right side air return opening should
follow the Upflow Specific Steps - Offset Installation to ensure the full
opening is available for return ductwork.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts, and servicing furnaces.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in property damage, personal
injury or death.
Missing or damaged gaskets on trap components may result in flue gas
leakage and water leakage.
Remove these for Horizontal Left
Remove these for Horizontal Right
Remove these for Upflow
NOTICE
!
Upflow installations utilizing the right side air return opening should
follow the Upflow Specific Steps - Offset Installation to ensure the full
opening is available for return ductwork.