912SE: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
NOTE:
1. A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in a factory - authorized accessory filter rack. See
accessory list. To determine airflow performance without this filter, assume an additional 0.1 in. w.c. available external static pressure.
2. Adjust the blower airflow settings as necessary for the proper air temperature rise for each installation.
3. Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return. A minimum filter size of 20” x 25” (508 x 635 mm) is required.
4. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return
5. The -- entry indicates unstable operating conditions
TYPICAL WIRING SCHEMATIC
A190079
FURNACE CONTROL BOARD
A210192
60120M24
1
Cont. Fan
770
665
545
445
355
275
185
-
-
-
2
830
725
615
515
425
345
265
180
130
-
3
915
815
725
615
525
445
370
295
220
165
4
990
895
810
710
620
540
465
395
325
255
5
1085
1000
915
835
740
655
580
510
445
380
6
1170
1095
1010
935
855
765
690
620
555
490
7
1235
1160
1080
1005
935
850
770
700
635
570
8
1330
1260
1190
1115
1050
980
900
820
755
695
9
1405
1335
1270
1200
1135
1070
1000
920
850
790
10
1490
1425
1365
1295
1235
1170
1110
1040
965
900
11
1585
1525
1470
1405
1340
1285
1230
1170
1105
1030
12
1665
1605
1550
1495
1435
1375
1320
1270
1210
1145
13
1750
1700
1645
1595
1535
1480
1425
1375
1320
1270
14
1835
1785
1740
1685
1630
1575
1525
1475
1430
1385
15
Heat
1880
1830
1780
1730
1680
1625
1575
1530
1480
1435
16
1920
1875
1825
1775
1730
1675
1625
1580
1535
1490
17
1995
1945
1900
1855
1810
1760
1715
1670
1625
1585
18
Cooling
2115
2065
2020
1975
1930
1875
1815
1750
1690
1630
Air Delivery - CFM (with filter) (Continued)
Unit Size
Airflow
Setting
Default
Setting
External Static Pressure (in. w.c.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
Airflow Settings
Default Airflow Settings
*
*. Setting #1 is the default setting for Constant Fan
Designated Airflow Settings
Unit Size
Heating
Cooling
Heating
Const. Fan
36040M14
8
18
(5-8)
(1-4)
36040M17
9
18
(4-9)
(1-1)
36060M14
12
18
(6-14)
(1-6)
42060M17
9
18
(7-14)
(1-8)
48080M17
11
17
(8-14)
(1-8)
60080M21
11
18
(7-14)
(1-8)
60100M21
13
18
(7-16)
(1-7)
66100M21
10
16
(7-12)
(1-8)
60120M24
15
18
(12-16)
(1-1)
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
COM
W
C
R
G
Y
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES:
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.