DRAIN PIPING WORK

Drain Piping Installation

Install the drain piping (see Fig. 10) and take steps to eliminate

condensation. Improperly rigged piping could lead to leaks and

eventually wet furniture and belongings.

1-1.5m

1

2

3~5ft

Fig. 10

 - 

Drain Piping Installation

Fig. 11

 - 

Hanging Bar

(1.) Hanging bar
(2.)

1/100 gradient

Install the Drain Pipes
IMPORTANT

: Observe all local sanitary codes when installing

condensate drains.

S

Keep piping as short as possible and slope it downwards
at a gradient of at least 1/100 so that air does not remain

trapped inside the pipe.

S

Keep the pipe size equal to or greater than that of the
connecting pipe (PVC pipe, nominal diameter 0.8 in.

(20mm), outside diameter .98 in. (25 mm)).

S

Push the drain hose as far as possible over the drain
socket, and tighten the metal clamp securely.

Fig. 12

 - 

Push the Drain Hose

1. Drain socket (attached to the unit)
2. Metal clamp
3. Drain hose
4. Insulation (field supply)

a. Insulate the drain hose inside the building.

b. If the drain hose cannot be sufficiently set on a slope, fit

the hose with the drain raising piping (field supplied).

c. Ensure the heat insulation work is executed on the

following two spots to prevent any possible water

leakage due to dew condensation:

(1.) Indoor drain pipe
(2.) Drain socket.

Unit: mm

1
2

5

7

~

0

5

1~1.5m

300/11.8in

6 5 4

3

ni

7.

8/

0

2

2

ni

5.

9

2/

0

5

7

ni

3

~

0

ni

9.

0

2/

0

3

5

3~5ft

Fig. 13

 - 

Drain Setup Pipe

1. Ceiling slab
2. Hanger bracket
3. Adjustable range
4. Drain raising pipe
5. Drain hose
6. Metal clamp

 Connect the drain hose to the drain raising pipes, and

insulate them.

 Connect the drain hose to the drain outlet on the indoor unit,

and tighten it with the clamp.

NOTE

:  Drain setup pipe:

S

The install height of the drain raising pipe should be less
than 21 in. (530 mm).

S

The drain raising pipe should form a right angle with the
unit. The distance to the unit should not exceed 11.81 in.

(300 mm).

S

To prevent air bubbles, install the drain hose level at an
angle slightly tilted upward (</3 in / 75 mm).

S

The drain hose incline should be 3 in (75 mm) or less so
the drain socket does not have to withstand additional force.

S

To ensure a downward slope of 1:100, install the hanging
bars every 3.3 ft. (1m) to /4.9 ft./(1.5 m).

S

When unifying the multiple drain pipes, install the pipes as
shown in Fig. 14. Select the converging drain pipes whose

gauge is suitable for the operating capacity of the unit.

1

T-joint converging drain pipes

0

3

5-

0

0

0

1

1

1

Unit: mm

Fig. 14

 - 

T

Joint Converging Drain Pipes

S

Connect the drain hose to the drain raising pipes, and
insulate them.

S

Connect the drain hose to the drain outlet on the indoor
unit, and tighten it with the clamp.

Summary of Contents for 619REQ009CBMA

Page 1: ...tual model may differ slightly NOTE Read the entire instruction manual before starting the installation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 DIMENSIONS IND...

Page 2: ...hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in...

Page 3: ...r than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection pipe before it enters the wall to the indoor unit This ensu...

Page 4: ...e of BX cable is not recommended Recommended Connection Method for Power and Communication Wiring Power and Communication Wiring The main power is supplied to the outdoor unit The field supplied 14 3...

Page 5: ...DY PANEL BODY PANEL BODY PANEL DIMENSIONS Height in mm 10 24 260 1 97 50 10 24 260 1 97 50 10 24 260 1 97 50 Width in mm 22 44 570 25 47 647 22 44 570 25 47 647 22 44 570 25 47 647 Depth in mm 22 44 5...

Page 6: ...6 CLEARANCES INDOOR Fig 3 Cassette Unit Clearance...

Page 7: ...it s If not reinforce the site prior to installation Refer to the install cardboard to determine where the location should be reinforced IMPORTANT To guarantee a good performance the unit must be inst...

Page 8: ...installing optional accessories review the optional accessories list in the installation manual Depending on field conditions it may be easier to install optional accessories before the indoor unit i...

Page 9: ...tion 1 Indoor drain pipe 2 Drain socket Unit mm 1 2 5 7 0 5 1 1 5m 300 11 8in 6 5 4 3 n i 7 8 0 2 2 n i 5 9 2 0 5 7 n i 3 0 n i 9 0 2 0 3 5 3 5ft Fig 13 Drain Setup Pipe 1 Ceiling slab 2 Hanger bracke...

Page 10: ...2 Water receiver When the electric wiring work is complete check the drainage flow during COOL running ElectricalWiring 1 Remove the indoor unit control box lid 2 Follow the Wiring Diagram label atta...

Page 11: ...with the supplied screws see Fig 19 1 Decoration panel 2 Screws M5 supplied with the panel 1 2 Fig 19 Attach the Decoration Panel 3 After installing the decoration panel ensure there is no space betw...

Page 12: ...x plug to be connected to Wired Controller s cable Grille Display 10 pin Molex plug to be connected to Control Board Grille Louver Motor Power 5 Pin Molex plug to be connected to Control Board Fig 23...

Page 13: ...1 46 Indoor unit powered by the outdoor unit Permissible limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps CONNECTION DIAGRAMS A150634 Fig 26 Connecti...

Page 14: ...3 5 8 15 88 50 to 60 67 7 to 81 3 Flare nut Copper tube A150770 Fig 31 Tighten the Flare Nut 6 Connect the drain line The drain line must not have a trap anywhere in its length The drain line must pit...

Page 15: ...the tubing where possible 2 Ensure the drain tube slopes downward along its entire length 3 Ensure all tubing and connections are properly insulated 4 Fasten the tubes to the outside wall when possibl...

Page 16: ...ent overload protection 2 times O F1 Open circuit or short circuit of outdoor ambient temperature sensor T4 3 times O F2 Open circuit or short circuit of condenser coil temperature sensor T3 4 times O...

Reviews: