—5—
SPECIFICATIONS Continued
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors per the NEC (ANSI/NFPA 70) Article
336-26. If other than uncoated (non-plated), 60° or 75°C (140° or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for
larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.
** Fan motor with ball bearings required. See Low-ambient controller Installation Instructions for application.
NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.
UNIT SIZE
042-C, D
048-C
060-C
Operating Weight (Lb)
206
199
217
ELECTRICAL
Unit Volts—Hertz—Phase
208–230—60—1
Operating Voltage Range*
197—253
Compressor— Rated Load Amps
19.0
24.4
28.8
Locked Rotor Amps
105.0
140.0
165.0
Condenser Fan Motor—Full Load Amps
1.4
1.4
1.4
Min Unit Ampacity for Wire Sizing
25.2
31.9
37.4
Min Wire Size (75°C Copper) AWG†
10
10
8
Min Wire Size (60°C Copper) AWG†
10
8
8
Max Wire Length (Ft) (75°C Copper)‡
73
59
78
Max Wire Length (Ft) (60°C Copper)‡
77
97
82
Max Branch Circuit Fuse Size**
40
50
60
COMPRESSOR and REFRIGERANT
Compressor—Manufacturer and Type
Copeland Reciprocating
Millennium Scroll
Millennium Scroll
Temperature and Current Protection
Internal Line Break
Internal Line Break and Dome Thermostat
Refrigerant—Type and Amount (Lb)††
R-22 and 5.51
R-22 and 7.63
R-22 and 10.63
CONDENSER COIL and FAN
Coil Face (Sq Ft)
12.2
15.2
18.3
Fins per In.—Rows—Circuits
20—1—2
25—1—3
25—1—4
Fan Motor—HP, Type, and RPM
1/4 PSC and 1100
Volts—Hertz—Phase
208/230—60—1
Condenser Airflow (CFM)
3000
OPTIONAL EQUIPMENT
Support Feet
KSASF0101AAA
Coastal Filter
KAACF0801MED
Time Delay Relay
KAATD0101TDR
Cycle Protector
KSACY0101AAA
Crankcase Heater
Standard
KAACH1201AAA
Start Assist—Capacitor/Relay Type
KSAHS1301AAA
KSAHS1601AAA
Start Assist—PTC Type
KAACS0201PTC
Sound Hood
KSASH1201COP
KSASH2001CYL
TXV Kit (RPB)
KAATX0501RPB
KAATX0601RPB
KAATX0701RPB
TXV Kits (Hard Shutoff)
KSATX0601HSO
KSATX0701HSO
Low-Pressure Switch
KAALP0101LPS
High-Pressure Switch
KSAHI0101HPS
Filter Drier
P502-8163S (RCD)
Evaporator Freeze Thermostat**
KAAFT0101AAA
Liquid-Line Solenoid Valve
KAALS0101LLS
Winter Start Control**
KAAWS0101AAA
Low-Ambient Kit
KSALA0201R22
MotorMaster® Control††
32LT660004 (RCD)
Ball Bearing Fan Motor
HC40GE232 (RCD)
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBPAC01-B
Builder’s Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
TSTATBBBAC01-B
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
TSTATBBPRH01-B
Outdoor Air Temperature Sensor
TSTATBBSEN01-B
Backplate for Non-Programmable
Thermostat
TSTATXXNBP01
Backplate for Programmable Thermostat
TSTATXXPBP01
Backplate for Builder’s Thermostat
TSTATXXBBP01
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
TSTATXXCNV10