![Bryant 581J Product Data Download Page 13](http://html1.mh-extra.com/html/bryant/581j/581j_product-data_2822131013.webp)
13
TABLE 9 – PHYSICAL DATA
(HEATING)
3 -- 6 TONS
581J*04A
581J*05A
581J*06A
581J*07A
Gas Connection
# of Gas Valves
1
1
1
1
Nat. gas supply line press (in. w.g.)/(PSIG)
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
4 ---13 / 0.18 --- 0.47
Propane supply line press (in. w.g.)/(PSIG)
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
11 ---13 / 0.40 --- 0.47
Heat Anticipator Setting (Amps)
1st stage
0.14
0.14
0.14
0.14
2nd stage
0.14
0.14
0.14
0.14
Natural Gas, Propane Heat
# of stages / # of burners (total)
1 or 2 / 2
1 or 2 / 2
1 or 2 / 2
2 / 2
LO
W
Connection size
1/2” NPT
1/2” NPT
1/2” NPT
1/2” NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise range (F)
25 --- 55
25 --- 55
20 --- 55
15 --- 55
# of stages / # of burners (total)
1 or 2 / 3
1 or 2 / 3
1 or 2 / 3
2 / 3
MED
Connection size
1/2” NPT
1/2” NPT
1/2” NPT
1/2” NPT
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise range (F)
55 --- 85
35 --- 65
30 --- 65
20 --- 50
Connection size
---
1 or 2 / 3
1 or 2 / 3
2 / 4
HI
G
H
# of stages / # of burners (total)
---
1/2” NPT
1/2” NPT
3/4” NPT
Rollout switch opens / closes
---
195 / 115
195 / 115
195 / 115
Temperature rise range (F)
---
50 --- 80
40 --- 80
30 --- 60
Low NO
x
Gas Heat
# of stages / # of burners (total)
1 or 2 / 2
1 or 2 / 2
1 or 2 / 2
---
LO
W
Connection size
1/2” NPT
1/2” NPT
1/2” NPT
---
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
---
Temperature rise range (F)
20 --- 50
20 --- 50
15 --- 50
---
# of stages / # of burners (total)
1 or 2 / 3
1 or 2 / 3
1 or 2 / 3
---
MED
Connection size
1/2” NPT
1/2” NPT
1/2” NPT
---
Rollout switch opens / closes
195 / 115
195 / 115
195 / 115
---
Temperature rise range (F)
30 --- 60
30 --- 60
25 --- 60
---
---
# of stages / # of burners (total)
---
1 or 2 / 3
1 or 2 / 3
---
HI
G
H
Connection size
---
1/2” NPT
1/2” NPT
---
Rollout switch opens / closes
---
195 / 115
195 / 115
---
Temperature rise range (F)
---
40 --- 70
35 --- 70
---
581J
Summary of Contents for 581J
Page 51: ...51 TYPICAL WIRING DIAGRAMS C08518 Fig 15 1 Stage Cooling Typical Power Diagram 581J ...
Page 52: ...52 TYPICAL WIRING DIAGRAMS cont C08577 Fig 16 2 Stage Cooling Typical Power Diagram 581J ...
Page 53: ...53 C08524 Fig 17 1 Stage Typical Wiring Diagram 581J ...
Page 54: ...54 C08578 Fig 18 2 Stage Typical Wiring Diagram 581J ...