Table 18—Fan Performance 581B 048, 581C 048 — Vertical Discharge Units; Standard Motor
(Belt Drive)*
AIRFLOW
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
CFM
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
666
0.26
257
778
0.37
367
871
0.47
471
952
0.57
572
1025
0.67
670
1300
701
0.31
306
810
0.43
426
901
0.54
540
981
0.65
651
1053
0.76
760
1400
737
0.36
361
842
0.49
491
931
0.62
616
1010
0.74
738
1081
0.86
856
1500
773
0.42
422
875
0.57
564
963
0.70
699
1040
0.84
831
1110
0.96
960
1600
810
0.49
491
909
0.65
643
994
0.79
790
1070
0.94
932
1140
1.08
1070
1700
847
0.57
567
943
0.73
730
1027
0.89
888
1101
1.05
1040
1170
1.20
1189
1800
885
0.66
652
978
0.83
826
1060
1.00
994
1133
1.16
1157
—
—
—
1900
923
0.75
745
1014
0.94
930
1093
1.11
1109
—
—
—
—
—
—
2000
962
0.85
847
1049
1.05
1043
—
—
—
—
—
—
—
—
—
AIRFLOW
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
1.2
1.4
1.6
1.8
2.0
CFM
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
1093
0.77
767
1155
0.87
861
1213
0.96
955
1268
1.05
1047
1321
1.14
1137
1300
1119
0.87
866
1181
0.98
970
1239
1.08
1073
1294
1.18
1175
—
—
—
1400
1147
0.98
972
1208
1.09
1086
—
—
—
—
—
—
—
—
—
1500
1175
1.09
1086
—
—
—
—
—
—
—
—
—
—
—
—
1600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1700
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
NOTES:
1.
Grey cells
indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See general fan performance notes.
LEGEND
Bhp
— Brake Horsepower
Watts
— Input Watts to Motor
*Motor drive range: 770 to 1185 rpm. All other rpms require field-supplied drive.