NOTES FOR FIG. 1, 2, 5, 6, 9
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7. For 208/230-3-60 v units: TRAN is wired for 230-v unit. If unit is to be
run with 208-v power supply, disconnect BLK wire from 230-v tap
(RED) and connect to 208-v tap (BLU). Insulate end of 230-v tap.
NOTES FOR FIG. 3, 4, 7, 8, 10
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
NOTES FOR FIG. 11
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7. For 208/230-3-60 v units: TRAN is wired for 230-v unit. If unit is to be
run with 208-v power supply, disconnect BLK wire from 230-v tap
(RED) and connect to 208-v tap (BLU). Insulate end of 230-v tap.
8.
NOTES FOR FIG. 12
1. If any of the original wire furnished must be replaced, it must be
replaced with Type 90 C wire or its equivalent.
2. Three-phase motors are protected under primary single-phasing
conditions.
3. Thermostat:
HH07AT170, 172, 174, and P272-2783
Subbase:
HH93AZ176, 178, and P272-1882, 1883
4. Set heat anticipator at 1 amp.
5. Use copper conductors only.
6. Use copper, copper-clad aluminum or aluminum conductors.
7.
CIRCUIT
BREAKER
VOLTS
MFG. PT. NO.
MUST
TRIP
AMPS
CB
24 V
Potter & Brumfield
3.2
W2BX-1024-3.2
CB1 150
460-3-60
Heinemann
Airpax
8.5
CF3-Z228-4
219-3-2600-486
CIRCUIT
BREAKER
VOLTS
MFG. PT. NO.
MUST
TRIP
AMPS
CB
24 V
Potter & Brumfield
3.2
W2BX-1024-3.2
CB1 150
460-3-60
Heinemann
Airpax
8.5
CF3-Z228-4
219-3-2600-486
Summary of Contents for 558F.36.1
Page 3: ... 3 Fig 1 Schematic Component Arrangement 558F036 048 208 230 1 60 ...
Page 4: ... 4 Fig 2 Schematic Component Arrangement 558F036 048 208 230 3 60 ...
Page 5: ... 5 Fig 3 Schematic Component Arrangement 558F036 048 460 3 60 ...
Page 6: ... 6 Fig 4 Schematic Component Arrangement 558F036 048 575 3 60 ...
Page 7: ... 7 Fig 5 Schematic Component Arrangement 558F060 208 230 1 60 ...
Page 8: ... 8 Fig 6 Schematic Component Arrangement 558F060 208 230 3 60 ...
Page 9: ...Fig 7 Schematic Component Arrangement 558F060 460 3 60 9 ...
Page 10: ...Fig 8 Schematic Component Arrangement 558F060 575 3 60 10 ...
Page 11: ...Fig 9 Schematic Component Arrangement 558F072 208 230 3 60 and 460 3 60 11 ...
Page 12: ... 12 Fig 10 Schematic Component Arrangement 558F072 575 3 60 ...
Page 13: ... 13 Fig 11 Schematic Component Arrangement 558F090 150 208 230 3 60 and 460 3 60 ...
Page 14: ... 14 Fig 12 Schematic Component Arrangement 558F090 150 575 3 60 ...
Page 20: ...Copyright 2000 Bryant Heating Cooling Systems CATALOG NO 5355 810 ...