![Bryant 551J Series Installation Instructions Manual Download Page 25](http://html.mh-extra.com/html/bryant/551j-series/551j-series_installation-instructions-manual_2822065025.webp)
25
DIP
Switch
Label
DIP
Switches
(3)
S-Bus
2 Pin Side
Connector
S-Bus
Terminals
(1 and 2)
C14178
Fig. 36 -- S--Bus Sensor DIP Switches
Table 5 – Enthalpy Control Sensor Wiring Terminations*
Terminal
Type
Description
Nbr
Label
1
S---BUS
S---BUS
S---Bus Communications
(Enthalpy Control Sensor Bus)
2
S---BUS
S---BUS
S---Bus Communications
(Enthalpy Control Sensor Bus)
* Terminals are polarity insensitive.
Table 6 – Enthalpy Control Sensor DIP Switch Settings
Use
DIP Switch Positions for Switches 1, 2, and 3
1
2
3
DA*
OFF
ON
OFF
RA
[
ON
OFF
OFF
OA**
OFF
OFF
OFF
* DA = Discharge Air
[
RA = Return Air
** OA = Outside Air
NOTE
: When a S--Bus sensor is connected to an existing
network, it will take 60 minutes for the network to
recognize and auto--configure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor
failures (except SAT) will be issued and no economizing
function will be available.
CO
2
Sensor Wiring —
When using a CO
2
sensor the black and brown common
wires are internally connected and only one is connected
to “IAQ COM” on the W7220. Use the power from the
W7220 to power the CO
2
sensor OR make sure the ground
for the power supplies are common. See Fig. 37 for CO
2
sensor wiring.
CO
2
SENSOR
24V
ANALOG
OUT
L1
(HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
–
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1
C14158
Fig. 37 -- Wiring for CO
2
Sensor
Interface Overview
This section describes how to use the economizer’s user
interface for:
S
Keypad and menu navigation
S
Settings and parameter changes
S
Menu structure and selection
User Interface —
The user interface consists of a 2--line LCD display and a
4--button keypad on the front of the economizer controller.
2 LINE
LCD
MENU UP
(EXIT)
BUTTON
SCROLL
UP/DOWN
BUTTONS
SELECT
(ENTER)
BUTTON
C14206
Fig. 38 -- W7220 Controller
Keypad —
The four navigation buttons (see Fig. 38) are used to scroll
through the menus and menu items, select menu items,
and to change parameter and configuration settings.
Summary of Contents for 551J Series
Page 4: ...4 C160142 Fig 2 Dimensional Drawing Sizes 07 09 ...
Page 5: ...5 C160143 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Page 6: ...6 C13302A Fig 3 Dimensional Drawing Sizes 11 and 12 ...
Page 7: ...7 C13303A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Page 39: ...39 a551J 006 Fig 41 RTU Open Controller Wiring Diagram ...
Page 53: ...53 ...