GUIDE SPECIFICATIONS

HORIZONTAL DISCHARGE OUTDOOR UNITS

Size Range: 3/4 to 2 1/2 Ton Nominal Cooling and Heating Capacity

Model Number: 538P

PART 1 - GENERAL

1.01 System Description

A. Outdoor air- cooled split system compressor sections suitable

for on- the- ground, rooftop, wall hung or balcony mounting.
Units shall consist of a rotary compressor, an air- cooled coil,

propeller- type draw- through outdoor fan, reversing valve
(HP), accumulator (HP units), metering device(s), and control

box. Units shall discharge air horizontally as shown on the
contract drawings. Units shall function as the outdoor

component of an air- to- air heat pump system.

B. Units shall be used in a refrigeration circuit matched to the

ductless heat pump fan coil units.

1.02 Agency Listings

A. Unit construction shall comply with ANSI/ASHRAE 15, latest

revision, and with the NEC.

B. Units shall be evaluated in accordance with UL standard 1995.
C. Units shall be listed in the CEC directory.
D. Unit cabinet shall be capable of withstanding 500- hour salt

spray test per Federal Test Standard No. 141 (method 6061).

E. Air- cooled condenser coils shall be leak tested at 550 psig.

1.03 Delivery, Storage, And Handling

Units shall be shipped in one piece and shall be stored and handled

per unit manufacturer’s recommendations.

1.04 Warranty (For Inclusion By Specifying

Engineer)

PART 2 - PRODUCTS

2.01 Equipment

A. General:

Factory assembled, single piece, air- cooled outdoor unit.

Contained within the unit enclosure shall be all factory wiring,

piping, controls, and the compressor.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of galvanized steel,

bonderized and coated with a baked- enamel finish on
inside and outside.

2. Unit access panels shall be removable with minimal screws

and shall provide full access to the compressor, fan, and

control components.

3. Outdoor compartment shall be isolated and have an acoustic

lining to assure quiet operation.

C. Fans:

1. Outdoor fans shall be direct- drive propeller type, and shall

discharge air horizontally. Fans shall draw air through the
outdoor coil.

2. Outdoor fan motors shall be totally- enclosed, single phase

motors with class B insulation and permanently- lubricated
ball bearings. Motor shall be protected by internal thermal

overload protection.

3. Shaft shall have inherent corrosion resistance.
4. Fan blades shall be non metallic and shall be statically and

dynamically balanced.

5. Outdoor fan openings shall be equipped with PVC

metal/mesh coated protection grille over fan.

D. Compressor:

1. Compressor shall be fully hermetic rotary type.
2. Compressor shall be equipped with oil system, operating oil

charge, and motor. Internal overloads shall protect the
compressor from over- temperature and over- current.

3. Motor shall be NEMA rated class F, suitable for operation

in a refrigerant atmosphere.

4. Compressor assembly shall be installed on rubber vibration

isolators.

5. Compressors shall be single phase.

E. Outdoor Coil:

Coil shall be constructed of aluminum fins mechanically bonded to

seamless copper tubes, which are cleaned, dehydrated, and sealed.

F. Refrigeration Components:

Refrigerant circuit components shall include brass external liquid

line service valve with service gage port connections, suction line

service valve with service gage connection port, service gage port

connections on compressor suction and discharge lines with

Schrader type fittings with brass caps, accumulator, reversing

valve.

G. Controls and Safeties:

Operating controls and safeties shall be factory selected, assembled,

and tested. The minimum control functions shall include the

following:

1. Controls:

a. A time delay control sequence is provided standard through

the fan coil board.

b. Automatic outdoor- fan motor protection.

2. Safeties:

a. System diagnostics.

b. Compressor motor current and temperature overload

protection.

c. Outdoor fan failure protection.

H. Electrical Requirements:

1. Unit shall operate on single- phase, 60 Hz power at 115 v

for unit sizes 09- 12 and 208- 230v for unit sizes 09, 12, 18,
24, and 30, as specified.

2. Unit electrical power shall be a single point connection.
3. Unit Control voltage to the indoor fan coil shall be 0- 15V

DC.

4. All power and control wiring must be installed per NEC

and all local electrical codes.

5. Unit shall have high- and low- voltage terminal block

connections.

Bryant Heating & Cooling Systems

D

7310 W. Morris St.

D

Indianapolis, IN 46231

Edition Date: 05/15

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: PDS538- 619P- 02

Replaces: PDS538- 619P- 01

Summary of Contents for 538PR

Page 1: ...ily room addition S Special space requirements S When changes in the load cannot be handled by the existing system S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structure is essential The ideal compliment to your ducted system when it is impractical or ...

Page 2: ...ll indoor units service and maintenance expense is reduced due to easy to use cleanable filters In addition these high wall systems have extensive self diagnostics to assist in troubleshooting BUILT IN RELIABILITY Ductless split system indoor and outdoor units are designed to provide years of trouble free operation The high wall indoor units include protection against freeze up and high evaporator...

Page 3: ...TO THE OUTDOOR UNIT B 1 1 Q A R SYSTEM TYPE Q HEAT PUMP VOLTAGE A 115 1 60 E 208 230 1 60 OUTDOOR UNIT 538 P MA 009 538 OUTDOOR UNIT P MODEL MA ALL MODELS NOMINAL CAPACITY 009 3 4TON 012 1TON 018 1 1 2TONS 024 2TONS 030 2 1 2TONS UNIT TYPE R OUTDOOR UNIT B MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B 1 1 Use of the AHRI Certified TM Mark indicates a manufacturer s p...

Page 4: ... Indoor Coil High Temp Protection in Heating Mode S Condenser High Temp Protection in Cooling Mode S Ease Of Service And Maintenance Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Application Flexibility Condensate Pumps A Crankcase Heater S Legend S Standard A Accessory INDOOR UNITS Fig 1 Condensate Pump Accessory On high wall fan coils the condensate pump has a lift capability of ...

Page 5: ...6 7 1186 10 2 258 13 4 343 40 8 18 5 DIMENSIONS OUTDOOR Fig 3 Outdoor unit Model W in mm D in mm H in mm L1 in mm L2 in mm Operating Weight lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 18K 32 3 845 12 6 320 27 6 700 22 1 560 13 2 335 102 5 46 5 24K 37 2 945 15 6 395 31 9 810 25 1 640 15 9 405 137 6 62 4 30K 37 2 945 15 6 395 31 9 810 25 1 640 15 9 405 157 6 71 5 ...

Page 6: ... 15m min 5 0 13m min 6 5 0 13m min 1 8m CEILING FLOOR Fig 4 Indoor Unit Clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Clearances Outdoor UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Page 7: ... 550 Metering Device Electronic Expansion Valve Capillary Tube Charge Lb 2 76 2 76 2 76 2 76 4 19 5 18 6 62 Outdoor Coil Face Area Sq Ft 9 2 9 2 9 2 9 2 16 0 21 1 17 2 No Rows 2 2 2 2 2 3 3 Fins per inch 21 21 21 21 18 18 17 Circuits 4 4 4 4 6 8 6 Indoor Coil Face Area sq ft Sq Ft 2 2 2 2 2 2 2 2 2 6 3 7 3 7 No Rows 2 2 2 2 2 3 3 Fins per inch 20 20 20 20 20 18 18 Circuits 3 3 3 3 4 7 7 Compressor...

Page 8: ... 8 69 8 66 7 62 6 53 5 81 Input 0 57 0 94 1 25 1 27 0 98 0 94 80 6F 27C 66 2F 19C TC 8 81 11 95 12 23 9 69 8 87 7 95 SC 7 49 8 32 8 63 7 85 6 64 6 04 Input 0 39 0 75 1 06 0 89 0 85 0 82 89 6F 32C 73 4F 23C TC 9 01 12 15 12 43 9 89 9 07 8 15 SC 7 7 8 53 8 84 8 06 6 85 6 25 Input 0 4 0 97 1 3 1 34 0 92 0 85 18 208 230V 69 8F 21C 59F 15C TC 12 58 15 24 16 25 11 04 8 32 6 78 SC 8 34 10 3 10 6 7 93 6 1...

Page 9: ... 0 83 64 4F 18C TH 12 1 12 7 12 32 11 34 10 32 9 32 8 81 6 14 Input 0 83 1 37 1 4 1 26 1 22 1 27 1 01 0 91 69F 20 5C TH 12 3 12 6 12 12 11 32 10 21 9 12 8 43 6 49 Input 0 83 1 1 1 12 1 19 1 19 1 25 1 03 0 98 71 6F 22C TH 11 1 12 4 12 01 11 21 10 01 9 02 8 21 6 01 Input 0 85 1 15 1 16 1 21 1 23 1 31 1 05 1 18 208 230V 59F 15C TH 23 2 20 5 19 42 17 56 16 52 14 28 12 08 9 39 Input 1 58 1 49 1 48 1 58...

Page 10: ...he base unit dimensional drawings for the location of mounting brackets SYSTEM OPERATING CONDITIONS Operating Range Min Max F C Cooling Heating Outdoor DB 4 122 20 50 4 86 20 30 Indoor DB 63 90 17 32 32 86 0 30 Indoor WB 59 84 15 29 Non Operating Temperature Range Min Max F C Indoor Outdoor DB 32 86 0 30 NOTE Reference the Product Installation Instructions for more information METERING DEVICES The...

Page 11: ...esult in equipment damage or improper operation S Wires should be sized based on NEC and local codes S Use copper conductors only with a minimum 300 volt rating and 2 64 inch thick insulation CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S E...

Page 12: ...34 27 42 34 27 46 5 40 33 50 45 39 50 45 39 Indoor Sound Pressure heating mode at different speeds dBa 40 33 26 41 34 27 40 33 26 41 34 27 45 39 32 47 44 38 47 44 38 Outdoor sound pressure level dBa 55 5 56 55 5 56 59 60 63 ELECTRICAL DATA UNIT SIZE OPER VOLTAGE MAX MIN COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP V PH HZ RLA V PH HZ FLA HP W V PH HZ FLA HP W 9K 127 104 115 1 60 5 3 115 1...

Page 13: ...60 Range of cur rent Amps 0 17 10 0 17 10 0 07 10 0 07 10 0 17 10 0 23 10 0 23 10 Rated current Amps 0 17 0 17 0 07 0 07 0 17 0 23 0 23 Rated HP HP 0 027 0 027 0 027 0 027 0 077 0 08 0 08 Speed rev min 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1300 1170 900 700 1250 1200 1100 900 250 1200 1100 900 Rated RPM rev min 1350 1350 1350 1350 1350 1350 1350 Max input W 25 25 ...

Page 14: ...oltage AC115V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC115V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum vo...

Page 15: ... 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum voltage between the lines DC5V CN14 Stepper motor interfac...

Page 16: ...r Voltage AC 230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10...

Page 17: ...output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_1 Ground CN8 Room temperature sensor interface maximum voltage DC5V CN9 Pipe temperature sensor interface maximum voltage DC5V CN10A Display interface maximum voltage between the lines DC5V CN14 Stepper motor interface optional maximum voltage between the line...

Page 18: ...e electric heating belt of chassis Fig 13 Wiring Diagram Size 30 208 230V INDOOR UNIT CONTROL BOARD INPUT or OUTPUT VALUE L_IN Power Voltage AC 230V CN11 Power Voltage AC230V CN16 Relative to the N terminal voltage DC 24V CN15 Maximum voltage DC5V CN6 Maximum output voltage AC230V CN4 Indoor fan interface Maximum voltage DC310V CN5 Stepper motor interface Maximum voltage between the lines DC12V P_...

Page 19: ...hall have the ability to act as the temperature sensing location for room comfort The unit shall have the following functions as a minimum 1 An automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start Stop 3 Temperature sensing controls shall sense return air temperature 4 Indoor coil free...

Page 20: ...l bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Fan blades shall be non metallic and shall be statically and dynamically balanced 5 Outdoor fan openings shall be equipped with PVC metal mesh coated protection grille over fan D Compressor 1 Compressor shall be fully hermetic rotary type 2 Compressor shall be equipped wit...