SPECIFICATIONS

 

* Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, reduce ratings 4 percent for each 1000 ft above sea level. Refer to 

National Fuel Gas Code Table F4 or furnace Installation Instructions. In Canada, derate the unit 10 percent for elevations 2000 ft to 4500 ft above sea level.

† Capacity and AFUE in accordance with U.S. government DOE test procedures.
‡ • Airflow shown is for bottom only return-air supply with factory-supplied 1-in. washable filter(s).

• For air delivery above 1800 CFM, see Air Delivery table for other options.
• An airflow reduction of up to 7% may occur when using the factory-specified 4-5/16-inch wide, high efficiency media filter.
• For best furnace efficiency when using the 4-5/16-inch wide media filter, adjust the blower speed tap to near the mid-point of the rise range.

** Time-delay type is recommended.
ICS—Isolated Combustion System
N/A—Not Applicable

 

UNIT SIZE

024045

036045

024070

036070

042091

048091

RATINGS AND PERFORMANCE

 

Input Btuh*

44,000

44,000

66,000

66,000

88,000

88,000

Output Capacity (Btuh)†

Nonweatherized ICS

35,000

35,000

53,000

53,000

71,000

71,000

AFUE†

Nonweatherized ICS

80.0

80.0

80.0

80.0

80.0

80.0

Certified Temperature Rise Range °F

25—55

15—45

40—70

30—60

40—70

30—60

Certified External Static Pressure

Heat/Cool

0.10/0.50

0.10/0.50

0.12/0.50

0.12/0.50

0.15/0.50

0.15/0.50

Airflow CFM‡

Heating

855

980

830

1140

1170

1445

Cooling

880

1250

880

1195

1360

1740

 

ELECTRICAL

 

Unit Volts—Hertz—Phase

115—60—1

Operating Voltage Range

Min—Max

104—127

Maximum Unit Amps

6.0

8.3

5.9

8.7

9.0

10.4

Maximum Wire Length (Measured 1 Way in Ft)

47

34

47

32

31

27

Minimum Wire Size

14

Maximum Fuse or Ckt Bkr Size (Amps)**

15

Transformer (24v)

40va

External Control

Heating

12va

Power Available

Cooling

35va

Air Conditioning Blower Relay

Standard

 

CONTROLS

 

Limit Control

SPST

Heating Blower Control

Solid-State Time Operation

Burners (Monoport)

2

2

3

3

4

4

Gas Connection Size

1/2-in. NPT

 

GAS CONTROLS

 

Gas Valve (Redundant)

White Rodgers

Min Inlet Pressure (In. wc)

4.5 (Natural Gas)

Max Inlet Pressure (In. wc)

13.6 (Natural Gas)

Ignition Device

Hot Surface

 

BLOWER DATA

 

Direct-Drive Motor HP (PSC)

1/5

1/3

1/5

1/3

1/3

1/2

Motor Full Load Amps

2.9

5.8

2.9

5.8

5.8

7.9

RPM (Nominal)—Speeds

1075—3

1075—4

1075—3

1075—4

1075—4

1075—4

Blower Wheel Diameter x Width (In.)

10 x 6

10 x 6

10 x 6

10 x 6

10 x 7

10 x 8

Filter Size (In.)—Permanent Washable (Supplied)

(1) 16 x 25 x 1

(1) 20 x 25 x 

1

 

FACTORY-AUTHORIZED DEALER-INSTALLED ACCESSORIES

 

Twinning Kit

N/A

 

KGATW0401HSI

 

Gas Conversion Kit—Natural-to-Propane

KGANP2001ALL

Gas Conversion Kit—Propane-to-Natural

KGAPN1601ALL

Air Cleaner

Model AIRA or 902B

Humidifier

Model HUM

Ventilator

Model VA3B, VB5B, VC5B, or VL3A

Summary of Contents for 395CAV

Page 1: ...nized steel and backed by a 20 year Limited Warranty INTELLIGENT CONTROL BOARD The 395CAV Furnace has an intelligent control board with an LED status indicator light to ensure top furnace performance...

Page 2: ...11 16 1 2 1 16 19 13 16 7 8 IN DIA POWER ENTRY AIRFLOW OUTLET 1 1 2 IN DIA R H GAS ENTRY 7 8 IN DIA ACCESSORY 1 2 IN DIA THERMOSTAT WIRE ENTRY SIDE INLET 141 2 1 231 4 SIDE RETURN DUCT LOCATION 11 4 T...

Page 3: ...Includes Outdoor Air Temperature Sensor ZONING 2 ZONE ZONEBB2KIT01 ZONEKIT2ZBDP ZONING 4 ZONE ZONEBB4KIT01 ZONING 8 ZONE ZONEBB8KIT01 320325 101 REV H MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCT...

Page 4: ...0 30 60 Certified External Static Pressure Heat Cool 0 10 0 50 0 10 0 50 0 12 0 50 0 12 0 50 0 15 0 50 0 15 0 50 Airflow CFM Heating 855 980 830 1140 1170 1445 Cooling 880 1250 880 1195 1360 1740 ELEC...