Bryant 38GRQ Installation Instruction Download Page 8

8

OUTDOOR UNIT INSTALLATION

1. Use a rigid base to support unit in a level position.
2. Locate outdoor unit and connect piping and wiring.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Excessive torque can break flare nut depending on

installation conditions.

Piping Connections to Outdoor Unit
IMPORTANT

:

Use refrigeration grade tubing ONLY. No other

type of tubing may be used. Use of other types of tubing will

void manufacturer’s warranty.

Make sure there is enough piping to cover the required length

between the outdoor and indoor unit.

Only use piping suitable for high side pressure for both high

side and low side connections.
Piping Guide:

S

Do not open service valves or remove protective caps from

tubing ends until all the connections are made.

S

Bend tubing with bending tools to avoid kinks and flat spots.

S

Keep the tubing free of dirt, sand, moisture, and other

contaminants to avoid damaging the refrigerant system.

S

Avoid sags in the suction line to prevent the formation of oil

traps. Insulate each tube with minimum 3/8- in. (10 mm) wall
thermal pipe insulation. Inserting the tubing into the insulation
before making the connections saves time and improves
installation quality.

1. Remove service valve cover if provided with unit.
2. Cut tubing with tubing cutter.
3. Install correct size flare nut onto tubing and make flare

connection.

4. Apply a small amount of refrigerant oil to the flare

connection on the tubing.

5. Properly align tubing in with service valve.
6. Tighten flare nut and finish installation using two wrenches

as shown in Fig. 11.

A07354

Fig. 11

-

Tighten Flare Nut

Strong

wind

A07350

Fig. 12

-

High Wind Installation

Outdoor Unit Wiring Connections

1. Mount outdoor power disconnect.
2. Run power wiring from main box to disconnect per NEC

and local codes. Set outdoor unit in place.

3. Remove field wiring cover from unit by removing screws.
4. Connect conduit to the conduit panel. (See Fig. 13)
5. Properly connect both power supply and control lines to

terminal block per the connection diagram.

6. Ground unit in accordance with NEC and local electrical

codes.

7. Use lock nuts to secure conduit.
8. Reinstall field wiring cover.

lock nut

Finish

conduit

Field Wiring Cover

Conduit Panel

A12539

Fig. 13

-

Field Wiring

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.

S

Be sure to comply with local codes while running wire

from indoor unit to outdoor unit.

S

Every wire must be connected firmly. Loose wiring may

cause terminal to overheat or result in unit malfunction.
A fire hazard may also exist. Therefore, be sure all wiring

is tightly connected.

S

No wire should be allowed to touch refrigerant tubing,

compressor or any moving parts.

S

Disconnecting means must be provided and shall be

located within sight and readily accessible from the air

conditioner.

S

Connecting cable with conduit shall be routed through

hole in the conduit panel.

Summary of Contents for 38GRQ

Page 1: ...OOR UNIT INSTALLATION 7 Install Mounting Plate 7 Drill Hole in Wall for Interconnecting Piping Drain and Wiring 7 OUTDOOR UNIT INSTALLATION 8 Piping Connections to Outdoor Unit 8 INSTALL ALL POWER INTERCONNECTING WIRING AND PIPING TO INDOOR UNIT 9 SYSTEM VACUUM AND CHARGE 9 START UP 11 WIRING DIAGRAMS 12 TROUBLESHOOTING 13 The following parts are included in your indoor unit Please contact your de...

Page 2: ...ust be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Do not bury more than 36 in 914 mm of refrigerant pipe in the ground If any section of pipe is buried there must be a 6 in 152 mm vertical rise to the valve con...

Page 3: ...ate shielded copper conductor only with a minimum 300 volt rating and 2 64 inch thick insulation must be used as the communication wire from the outdoor unit to the indoor unit Please use a separate shielded 16GA stranded control wire CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Wires should be sized based on NEC and local co...

Page 4: ...4 DIMENSIONS INDOOR Fig 1 Indoor Unit Dimensions Table 4 Indoor Unit Dimensions Model W H D Q 09 12K 37 4 5 12 3 5 8 2 1 6 18K 37 4 5 12 3 5 8 2 3 4 ...

Page 5: ...5 DIMENSIONS OUTDOOR Fig 2 Outdoor Unit Sizes 9 and 12 Fig 3 Outdoor Unit Size 18 ...

Page 6: ... min 6 5 0 13m min 1 8m CEILING FLOOR Fig 4 Indoor Unit Clearances CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Outdoor Unit Clearances Table 5 Outdoor Clearances UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Page 7: ...n Fig 6 3 If the wall is block brick concrete or similar material drill 2 5 mm diameter holes and insert anchors for the appropriate mounting screws 4 Attach the mounting plate to the wall Fig 6 09 and 12K Mounting Plate Spacing Wall Wall Mark middle Level Rear piping hole Rear piping hole See Hole Size Tables See Hole Size Tables 6 in 6 in Fig 7 18K Mounting Plate Spacing DRILL HOLE IN WALL FOR I...

Page 8: ...d make flare connection 4 Apply a small amount of refrigerant oil to the flare connection on the tubing 5 Properly align tubing in with service valve 6 Tighten flare nut and finish installation using two wrenches as shown in Fig 11 A07354 Fig 11 Tighten Flare Nut Strong wind A07350 Fig 12 High Wind Installation Outdoor Unit Wiring Connections 1 Mount outdoor power disconnect 2 Run power wiring fro...

Page 9: ...tion then fasten piping and wiring to the wall as required Completely seal the hole in the wall Fig 16 Remove Knockouts Mounting plate Fixing hook Mounting plate A12408 Fig 17 Hang Indoor Unit UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump CAUTION Refrigerant tubes and indoor coil should be eva...

Page 10: ...in any liquid water Refer to Fig 21 and proceed as follows 1 Pump system down to 28 in of mercury and allow pump to continue operating for an additional 15 minutes 2 Close service valves and shut off vacuum pump 3 Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig 4 Close service valve and allow system to stand for 1 hr During this time dry nitrogen will b...

Page 11: ...hts work properly 3 Does the air deflection louver function properly 4 Does the drain work OUTDOOR UNIT 1 Are there unusual noises or vibrations during operation Explain Following Items To Customer With The Aid Of The Owner s Manual 1 How to turn air conditioner on and off selecting COOLING HEATING and other operating modes setting a desired temperature setting the timer to automatically start and...

Page 12: ...2 8 0 2 C D V w o L 0 6 1 0 3 2 8 0 2 0 6 1 0 3 2 8 0 2 0 6 1 0 3 2 8 0 2 0 6 1 0 3 2 8 0 2 C D V w o L 0 6 1 0 3 2 8 0 2 k c o l B l a n i m r e T t i n U r o o d n I 8 1 e z i S k c o l B l a n i m r e T t i n U r o o d t u O 8 1 e z i S Power to Indoor Unit Control to Indoor Unit Power to Indoor Unit Main Power Supply Main Power Supply 208 230 1 60 Connection Diagram CONNECTING CABLE OUTDOOR TO...

Page 13: ...protection of outdoor unit Other malfunction E5 Module current protection Other malfunction H5 Module temperature protection Other malfunction P8 Freeze prevention protection Other malfunction E2 High power protection Other malfunction L9 Lacking inverse phase protection of compressor Other malfunction U2 PFC current malfunction Other malfunction HC High DC bus bar voltage protection Other malfunc...

Page 14: ...BDP S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Edition Date 06 15 Catalog No GRQ 619FB 01SI Replaces NEW ...

Reviews: