Bryant 333BAV Service And Maintenance Procedures Manual Download Page 8

Fig. 10—Service Label

A99149

SERVICE

11

12

13

14
21

22

23

24

31

32

33

34

43

45

LED CODE

STATUS

COMPONENT TEST

HUM

G

R

Y/Y2

W/W1

C

W2

OM

24 V

LED

TWIN
TEST

123

4

OF

F

If status code recall is needed, do not remove power or blower door. Briefly remove and
then reconnect one main limit wire to display stored status code.

NO PREVIOUS CODE - Stored status codes are erased when power
(115VAC or 24VAC) to control is interrupted or 48 hours after each fault is cleared.
BLOWER ON AFTER POWER UP (115VAC or 24 VAC) - Blower runs for 90 seconds,
if unit is powered up during a call for heat (R-W closed).
LIMIT OR FLAME ROLL-OUT SWITCH LOCKOUT - Control will auto reset after three
hours. Reset switch or replace fuse link. Refer to #33
IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34
GAS HEATING LOCKOUT - Control will NOT auto-reset.
Check for: 

- Mis-wired gas valve 

- Defective control (valve relay)

ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared.
Check for: 

- Leaky gas valve 

- Stuck-open gas valve

PRESSURE SWITCH DID NOT OPEN     Check for:
- Obstructed pressure tubing 

- Pressure switch stuck closed.

SECONDARY VOLTAGE FUSE IS OPEN
Check for: - Short-circuit in secondary voltage (24VAC) wiring
HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED
Check for: - Control relay may be defective

- Refer to #32

LOW HEAT PRESSURE, DRAFT SAFEGUARD, AUX-LIMIT (when used*) SWITCH DID NOT
CLOSE OR REOPENED (DOWNFLOW ONLY*)
 If open longer than five minutes,
inducer shuts off for 15 minutes before retry. Check for:
- Proper vent sizing 

- Low inducer voltage (115VAC)

- Defective Blower motor or capacitor 

- Defective inducer motor

- Defective pressure switch 

- Restricted vent

- Inadequate combustion air supply 

- Excessive wind

- Disconnected or obstructed pressure tubing            If it opens after trial for ignition
period, blower will come on for 90 second recycle delay.
LIMIT OR FLAME ROLL-OUT SWITCH IS OPEN - If open longer than three
minutes, code changes to #13. Flame roll-out switch requires manual reset.
Check for:    - Dirty filter or restricted duct system.        - Loose blower wheel.
- Defective blower motor or capacitor.

- Defective switch or connections.

- Inadequate combustion air supply (Flame Roll-out Switch or fuse link open).
- Open Flame Roll-out switch, or fuse link.   Manual reset or replace.
IGNITION PROVING FAILURE - Control will try three more times before lockout #14
occurs. If flame signal is lost after trial for ignition period, blower will come on for
90 second recycle delay. Check for: - Gas valve defective or gas valve turned off.
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal in
  HIGH HEAT).             - Green wire MUST be connected to furnace sheet metal.
- Flame sensor must be ungrounded.

- Manual valve shut-off.

- Defective Hot Surface Ignitor

- Control ground continuity.

- Inadequate flame carryover or rough ignition.            - Low inlet gas pressure.
LOW-HEAT PRESSURE, DRAFT SAFEGUARD, OR AUXILIARY LIMIT (when used*) SWITCH
OPEN WHILE HIGH HEAT PRESSURE SWITCH IS CLOSED 
     Check for:
- Disconnected or obstructed pressure tubing
- Pressure switch stuck open 

- Refer to #32 and #33

REPLACE CONTROL

EACH OF THE FOLLOWING STATUS CODES IS A TWO-DIGIT NUMBER WITH THE FIRST DIGIT DE-
TERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF
LONG FLASHES.

CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC1 and SEC2.
CONTINUOUS ON -

Control has 24VAC power.

RAPID FLASHING -

Line voltage (115VAC) polarity reversed. If twinned, refer to
twining kit instructions.

To initiate the component test sequence, shut "OFF" the room thermostat or
disconnect the "R" thermostat lead. Briefly short TWIN/TEST terminal to
"Com 24 V" Terminal. Status LED will turn off, control will turn "ON" the inducer motor-
low speed, inducer motor-high speed, hot surface ignitor, blower motor-low gas
heat speed, blower motor-high gas heat speed and blower motor-high cool
speed for 7-15 seconds each. Gas valve and humidifier will not be turned on.

320893-101 REV. D (LIT)

*

—8—

Summary of Contents for 333BAV

Page 1: ...afety glasses and work gloves Have fire extinguisher available during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see thi...

Page 2: ...at periodic maintenance be performed on this equipment Consult your local dealer as to the proper frequency of maintenance and the availability of a maintenance contract WARNING Never store anything o...

Page 3: ...el should not be dropped or bent as balance will be affected 8 Remove blower wheel from housing a Mark cutoff plate location to ensure proper reassembly b Remove screws holding cutoff plate and remove...

Page 4: ...tight with crimping tool or strike with ball peen hammer TIGHTNESS IS VERY IMPORTANT 4 Remove metal screw fitting from wire brush to allow insertion into cable b Clean each heat exchanger cell 1 Attac...

Page 5: ...4 v circuit contains an automotive type 3 amp fuse located on the main control Any 24 v electrical shorts during installation service or maintenance could cause this fuse to blow If fuse replacement i...

Page 6: ...at for dehumidification in cooling optional NOTES 1 2 3 4 5 NOTE 4 O NOTE 5 GREEN DEHUM Fig 7 Heating and Cooling Application Wiring Diagram for Single Stage Thermostats and or Single Speed Condensing...

Page 7: ...WIN TEST 1 CIRCUIT TWINNING BUSS CONNECTOR ALSO STATUS CODE RECALL NOTE 17 JUNCTION TERMINAL CONTROL TERMINAL FACTORY POWER WIRING 115VAC FACTORY CONTROL WIRING 24VAC FIELD POWER WIRING 115VAC FIELD C...

Page 8: ...AME ROLL OUT SWITCH IS OPEN If open longer than three minutes code changes to 13 Flame roll out switch requires manual reset Check for Dirty filter or restricted duct system Loose blower wheel Defecti...

Page 9: ...8 in wc for high stage gas heat Check for proper orifice size Control will attempt to light burners 4 times approximately 1 minute between attempts Code 34 Voltage is present at the gas valve for 7 se...

Page 10: ...10...

Page 11: ...11...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: