
Residential Air Conditioners and Heat Pumps Using R-22 and Puron® Refrigerant: Application Guideline and Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
Thermostatic Expansion Valve (TXV)
All (post-2006) furnace coils, most fan coils and a few heat pumps have
a factory installed thermostatic expansion valve (TXV). The TXV will
be a bi-flow, hard-shutoff with an external equalizer and a balance port
pin. A hard shut-off TXV does not have a bleed port. Therefore,
minimal equalization takes place after shutdown. TXVs are specifically
designed to operate with Puron or R-22 refrigerant, use only factory
authorized TXV’s. Do not interchange Puron and R-22 TXVs.
TXV Operation
The TXV is a metering device that is used in air conditioning and heat
pump systems to adjust to changing load conditions by maintaining a
preset superheat temperature at the outlet of the evaporator coil. The
volume of refrigerant metered through the valve seat is dependent upon
the following:
1. Superheat temperature is sensed by cap tube sensing bulb on
suction tube at outlet of evaporator coil. This temperature is
converted into pressure by refrigerant in the bulb pushing
downward on the diaphragm which opens the valve via the
pushrod(s).
2. The suction pressure at the outlet of the evaporator coil is
transferred via the external equalizer tube to the underside of the
diaphragm. This is needed to account for the indoor coil pressure
drop. Residential coils typically have a high pressure drop, which
requires this valve feature.
3. The pin is spring loaded, which exerts pressure on the underside of
the diaphragm. Therefore, the bulb pressure works against the
spring pressure and evaporator suction pressure to open the valve.
If the load increases, the temperature increases at the bulb, which
increases the pressure on the top side of the diaphragm. This opens
the valve and increases the flow of refrigerant. The increased
refrigerant flow causes the leaving evaporator temperature to
decrease. This lowers the pressure on the diaphragm and closes the
pin. The refrigerant flow is effectively stabilized to the load demand
with negligible change in superheat.
Install TXV
The thermostatic expansion valve is specifically designed to operate
with a refrigerant type. Do not use an R-22 TXV on a Puron system, and
do not use a Puron valve on an R-22 system. Refer to Product Data Sheet
for the appropriate TXV kit number.
IMPORTANT:
The TXV should be mounted as close to the indoor coil
as possible and in a vertical, upright position. Avoid mounting the inlet
tube vertically down. The valve is more susceptible to malfunction due
to debris if inlet tube is facing down. A factory-approved filter drier
must be installed in the liquid line at the indoor unit.
Installing TXV in Place of Piston in a Rated Indoor Coil
(pre-2006)
1. Pump system down to 2 psig, if possible, and recover refrigerant.
2. Remove hex nut from piston body. Use backup wrench on fan coils.
3. Remove and discard factory-installed piston. Be sure Teflon seal is
in place.
4. Reinstall hex nut. Finger tighten nut plus 1/2 turn.
NOTE:
If the piston is not removed from the body, TXV will not
function properly.
5. Install TXV on indoor coil liquid line. Sweat swivel adapter to inlet
of indoor coil and attach to TXV outlet. Use backup wrench to
avoid damage to tubing or valve. Sweat inlet of TXV, marked “IN”
to liquid line. Avoid excessive heat which could damage valve.
6. Install vapor elbow with equalizer adapter to suction tube of line set
and suction connection to indoor coil. Adapter has a 1/4-in. male
connector for attaching equalizer tube.
7. Connect equalizer tube of TXV to 1/4-in. equalizer fitting on vapor
line adapter.
8. Attach TXV bulb to horizontal section of suction line using clamps
provided. Insulate bulb with field-supplied insulation tape. See
for correct positioning of sensing bulb.
9. Proceed with remainder of unit installation.
A08083
Fig. 27 – Position of Sensing Bulb
Replacing TXV on an Indoor Coil (pre-2006)
1. Pump system down to 2 psig, if possible, and recover refrigerant.
2. Remove coil access panel and fitting panel from front of cabinet.
3. Remove TXV support clamp using a 5/16-in. nut driver. Save the
clamp.
4. Remove R-22 TXV using a backup wrench on flare connections to
prevent damage to tubing.
5. Using wire cutters, cut equalizer tube off flush with vapor tube
inside cabinet.
6. Remove bulb from vapor tube inside cabinet.
7. Braze equalizer stub-tube closed. Use protective barrier as
necessary to prevent damage to drain pan.
IMPORTANT:
Route the equalizer tube of TXV through suction line
connection opening in fitting panel prior to replacing fitting panel
around tubing.
8. Install TXV with 3/8-in. copper tubing through small hole in
service panel. Use wrench and backup wrench, to avoid damage to
tubing or valve, to attach TXV to distributor.
9. Reinstall TXV support clamp (removed in item 3).
10. Attach TXV bulb to vapor tube inside cabinet, in same location as
original was when removed, using supplied bulb clamps (nylon or
for correct positioning of sensing bulb.
11. Route equalizer tube through suction connection opening (large
hole) in fitting panel and install fitting panel in place.
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Al indoor coil units must be installed with a hard shut off Puron TXV
metering device.
CAUTION
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Use a brazing shield and wrap TXV with wet cloth or use heat sink
material
2 O’CLOCK
10 O’CLOCK
SENSING BULB
STRAP
SUCTION TUBE