7
ELECTRICAL DATA
UNIT SIZE
--- SERIES
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MIN
WIRE
SIZE
{
MIN
WIRE
SIZE
{
MAX
LENGTH
ft (m)
}
MAX
LENGTH
ft (m)
}
MAX
FUSE**
or CKT
BRK
AMPS
MAX
MIN
LRA
RLA
FLA
60
°
C
75
°
C
60
°
C
75
°
C
018---B
208/230/1
253
187
48.0
9.0
0.5
11.7
14
14
67 (20.4)
64 (19.5)
20
024---B
58.3
13.5
0.7
17.5
14
14
45 (13.7)
43 (13.1)
25
030---B
73.0
14.1
0.7
18.3
14
14
43 (13.1)
41 (12.5)
25
036---B
79.0
16.7
1.1
21.9
12
12
57 (17.4)
54 (16.5)
35
042---B
112.0
17.9
1.3
23.7
10
10
84 (25.6)
80 (24.4)
40
048---B
117.0
21.8
1.3
28.5
10
10
70 (21.3)
67 (20.4)
45
060---B
134.0
26.4
1.3
34.3
8
8
91 (27.7)
86 (26.2)
50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30° C, consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60° C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60 or 75° C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
}
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER (dBA)
UNIT SIZE ---
SERIES
STANDARD
RATING
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125
250
500
1000
2000
4000
8000
018---B
67
51.0
58.0
60.5
60.0
59.5
52.5
47.0
024---B
66
55.0
55.5
59.5
61.0
59.0
54.5
47.0
030---B
68
56.0
58.5
63.0
61.0
60.0
52.5
45.0
036---B
70
62.5
62.0
64.5
63.0
60.5
55.5
49.0
042---B
70
61.5
60.5
62.0
63.5
61.0
55.5
51.0
048---B
71
61.5
62.5
63.0
64.0
62.0
57.5
51.5
060---B
73
59.5
63.0
64.0
67.0
63.0
58.0
53.5
NOTE
: Tested in accordance with ARI Standard 270---95. (Not listed with ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---SERIES
REQUIRED SUBCOOLING
_
F (
_
C)
018---B
9 (5.0)
024---B
9 (5.0)
030---B
13 (7.2)
036---B
8 (4.4)
042---B
10 (5.6)
048---B
8 (4.4)
060---B
14 (7.8)
165A