4.2.6
LONWORKS
Commissioning may only be performed by
the LonWorks administrator.
4.2.6.1
COMMISSIONING PROTONODE
FPC-N35 ON A LONWORKS
NETWORK
The User will be prompted by the LonWorks
Administrator to hit the Service Pin on the
ProtoNode FPC-N35 at the correct step of
the Commissioning process which is
different for each LonWorks Network
Management Tool.
Figure 24 - LonWorks Service Pin Location
If an XIF file is required, see steps in
4.2.6.2
Instructions to Upload XIF File
from the UCG (LER) using Field
Server GUI Web Server
•
•
Open a web browser and go to the
following address: IP address of
ProtoCessor/fserver.xif
•
Example: 192.168.1.24/fserver.xif
•
If the web browser prompts you to
save file, save the file onto the PC. If
the web browser displays the xif file
as a web page, save the file on your
PC as fserver.xif. See Figure 20.
Figure 25 - Sample of Fserver.XIF File Being Generated