background image

 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: [email protected] Web: www.broycecontrol.com 

                   The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.

 

 

ELR01PN_30PN-1-A.DOCX 

Page 

1

 of 

1811 

 

 

       

  

 

 

 
 
 

 

 

 

 

 

 

 

 

                                                                                                                                                                                                                                                                                                                                    
 
 
 
 
 
 
 

 

 
 
 
 

 

 

Dims: to DIN 
43880 
W. 44mm 

 

FUNCTION DIAGRAMS 

 

The following operational modes are either enabled using the app or by adding external links 

 

 

Latching mode (factory default) 

 

 

 

 

 

Auto-reset mode (enabled via app) 

 

 

 

 
 

 

 

                                    

       

 
 

Terminal 
Protection 
to IP20 

 

 

 

Programmable user settings/adjustments 

 

Built-in NFC (Near Field Communication) allows user to access and change settings via 
compatible Smartphone/Device with installed app^ as well as retrieve historical data 

 

Two models available 6mA – 1A (ELR01PN) and 30mA – 30A (ELR30PN) – True R.M.S. 
measurements 

 

Option to select alternative toroid ratio, tripping method (latch or auto-reclosure modes),  
Output relay logic (pre-alarm, energise or de-energise on trip) and filter cut-off points 

 

Connection facility for remote “Test” and “Reset” push buttons or N.O. contacts 

 

Toroid open and short-circuit detection forces unit to trip (Red LED flashes during this condition) 

 

2 Relay outputs – Relay 1 (SPDT) and Relay 2 (SPNO) - User configurable 

 

Wide auxiliary operating supply voltage - 24 – 230V AC/DC 

 

Compliant with IEC 60947-2 / Annex M 

Type: ELR01PN/30PN 

Earth Leakage Relay – Type A (with NFC Technology)

 

^ App available from: 

 

 

 

 

 

 

Continued….. 

 

Auto-reclosure mode (enabled via app) 

 

 

 

 

Pre-Alarm mode (enabled via app) 

 

 

 

Note: relays are shown operating in their factory default states i.e. RLY1 = Standard Output 
and RLY2 = Positive Safety Output (Pre-Alarm default states are RLY1 and RLY2 = Standard 
Output) 

                                  

 

Aux. Supply

5, 7

13

12

14

Pre-alarm trip

level (50% x I n)*

t

Fault Current

10

11

Test/Reset button

t

25%

50%

75%

ELR_PA0216

RLY1

RLY2

Trip level (I n)

Reset level

Reset

Test

Reset

 

OVERVIEW 

 

The ELR…PN is a fully featured, Earth Leakage Relay that can either be easily configured using the built-in pre-defined “Profiles” or tailored specifically to suit the 
application. The app^ allows the user to define how the unit should operate (see Function diagrams below) as well as configure and set parameters such as the toroid 
ratio, relay logic (i.e. energise or de-energise on trip) and define how the Auto-Reclosure mode should operate. Additionally, the option to set a filter cut-off point can 
also be defined therefore allowing the unit to ignore signals above a certain frequency.  
 Utilising NFC technology allows the unit to be used in a “Passive” mode whereby settings can be made in the app and written to the unit without the need for the unit 
to be powered. This feature is useful where a panel needs to be shut down and power removed (for safety reasons) before any work or alterations need to be made. 
The user also has the ability to read back the configuration of a unit using the app in order to establish/check the settings. Additionally, it is possible to measure (and 
display) the actual leakage current present in the system.  
 An option to recall previous tripping information (accessed via the Logs option in the app) provides the user with historical data allowing the user to establish a pattern 
in the tripping occurrence’s and hence make any necessary adjustments. 
 