3.7 Control Outputs
3.7.1 Control Output Specifications
The CIE control outputs are listed in Table 30
Table 30 Control Output Specifications
Module
Item
Qty
Type
Voltage
Current
Rating
Fuse
Main Control Board
SUB880
MDH Output
1
Dry-contact,
N/C
30V
5A
M205, 5A, fast blow
ACF Output
1
24V output
24V
500mA
Poly resettable,
500mA
External Strobe Output
1
24V output
24V
1A
Poly resettable, 1A
Alarm Devices Output
1
Dry-contact
110V RMS
5A
No
24V output
24V
2A
Poly resettable, 2A
Backup Power Output
2
24V output
24V
4A
M205, 3A, fast blow
in total.
Common Alarm Relay
Output
1
Dry-contact
30V
2A
No
Common Fault Relay
Output
1
Dry-contact
30V
2A
No
Common Disablement
Relay Output
1
Dry-contact
30V
2A
No
Power Fail Relay Output
1
Dry-contact
30V
2A
No
4 Supervised
Output Expansion
Board SUB886
Optional Supervised
Outputs
4
Dry-contact
30V
2A
No
24V output
24V
2A
Poly resettable, 2A
Eight Relay
Expansion Board
SUB885
Optional Dry Contact Relay
Output
8
Dry-contact
30V
2A
No
OWS Plug-in
Module SUB888
Optional Dual Strobe
Output
1
Power
output,
polarity
reversible
24V
2A
Poly resettable, 2A
3.7.2 Dry Contacts Relay and Voltage Outputs
The non-monitored outputs include the following:
•
MDH output,
•
Common alarm relay output,
•
Common fault relay output,
•
Common disablement relay output,
•
Power Fail relay output.
•
Optional 8 relay outputs expansion board SUB885,
If any output listed above was monitored by external equipment, the installation circuit should meet the
requirements of the external equipment.