† Countdown timer can be set between 0 and 95 seconds in 5 sec increments
†
†
At the end of the count down, a relay on the timer board activates for switching of external equipment
or any other application.
For more details, refer to technical datasheets TDS005, TDS025 and block wiring diagram shown in this
manual in Figure 20 page 56 and Figure 21 page 57.
4.9.3
Local Control Station BLC1
Figure 16 Local Control Station BLCS1
General
The Local Control Station (BLCS1) provides for the manual release and discharge inhibit of the gas
extinguishing agent.
BLCS1 is interfaced to Brooks FT2GAS control panel via a supervised 4 wire connection.
The GAS RELEASE function provides a manual initiate switch, incorporating a two-step action which
initiates the normal system discharge sequence including fire and evacuation alarms, time delays, and
equipment shutdowns and overrides the discharge inhibit switch. The operation of this switch has a
visual indication at both the LCS and FT2Gas panel
The GAS ISOLATE function provides a discharge inhibit switch that prevents automatic discharge of the
extinguishing agent; stops and resets the normal system actuation control sequence; but does not
override the operation of the manual initiate switch. The operation of this switch causes an audible and
visual indication at the LCS and a visual indication at the FT2GAS panel
The BLCS1 has been designed to be highly visible to the occupants when placed adjacent to the main
entry to the protected area.
Features
•
Attractive design concept
•
Built in audible warning for gas isolate