EIB605C 191110
Sydney - Melbourne - Adelaide - Brisbane - Perth - Hobart - Darwin - New Zealand
fire products and solutions
Model
EIB605C Optical
Installation & Placement
Alarms should be placed in accordance with the general guidelines shown in
the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector
Please consult the Instruction Leaflet supplied with the EIB605C for detailed
instructions as to how to correctly install and position the smoke detector
Important Precaution:
Do not install the actual smoke/heat
alarm itself in new or renovated
buildings until all work is completed
(including floor coverings) and the
building
has
been
fully
cleaned.
(Excessive dust and debris from
building work can contaminate the
smoke chamber and cause problems,
and it will also invalidate the guarantee).
If it must be installed, cover it
completely, particularly around the
edges, with a dust cover (eg. a plastic
bag), until all cleaning is finished..
Specifications are subject to change
Technical Specification
Sensor:
Optical, uses light scatter from
smoke particles
Sensitivity:
Complies with the requirements of
BS EN 14604: 2005
Airspeed:
Essentially immune to the effect
of airspeed.
Button Test:
Simulates the effect of smoke to
check the chamber, electronics
and horn.
Hush:
Silences
nuisance
alarm.
Automatically
resets
after
approximately 10 minutes.
Supply Voltage:
9V Battery
Power-On Indicator:
Red LED flashes through cover
every 40 seconds
Alarm:
Piezoelectric-horn (built-in)
Alarm Sound Output:
85dB (minimum) at 3m
Temperature Range:
0 to 40°C
Humidity Range:
15% to 95% Relative Humidity –
non condensing
Interconnect:
Hardwire interconnect up to 12
battery powered alarms.
A combination of up to 12 battery
and Mains powered alarms maybe
interconnected.
Fixing:
Screw fixings supplied
Dimensions:
115mm
(diameter)
x
45mm
(height)
Weight:
200 grams
Warranty:
5 year (limited) warranty
Approvals:
Certified to AS3786
VdS approved to
BS EN14604:2005, CE approved,
Manufactured to ISO 9001:2000
quality standards.
Specifications are subject to change