Model

EIB605C Optical 

Installation & Placement 

         

Alarms should be placed in accordance  with the general guidelines shown in 
the  diagram  above.  These  recommendations  are  based  on  the  problem  of  
areas  of  “dead  air”  close  to  corners  of  rooms  and  apexes  of  ceilings,  which 
could result in the prevention of smoke reaching the smoke detector 

Please  consult  the  Instruction  Leaflet  supplied  with  the  EIB605C  for  detailed 
instructions as to how to correctly install and position the smoke detector 

Important Precaution: 

Do  not  install  the  actual  smoke/heat 
alarm  itself  in  new  or  renovated 
buildings  until  all  work  is  completed 
(including  floor  coverings)  and  the 
building 

has 

been 

fully 

cleaned. 

(Excessive  dust  and  debris  from 
building  work  can  contaminate  the 
smoke  chamber  and  cause  problems, 
and it will also invalidate the guarantee). 
If  it  must  be  installed,  cover  it 
completely,  particularly  around  the 
edges,  with  a  dust  cover  (eg.  a  plastic 
bag), until all cleaning is finished..  

Specifications are subject to change 

Technical Specification 

Sensor:

Optical,  uses  light  scatter  from 
smoke particles

Sensitivity:

 

Complies  with  the  requirements  of 
BS EN 14604: 2005 

Airspeed:

 

Essentially immune to the effect 

 

of airspeed. 

Button Test:

 

Simulates the effect of smoke to 
check  the  chamber,  electronics 
and horn. 

Hush:

Silences 

nuisance 

alarm. 

Automatically

resets 

after 

approximately 10 minutes. 

Supply Voltage: 

9V Battery 

Power-On Indicator:

  Red  LED  flashes  through  cover 

every 40 seconds 

Alarm:  

Piezoelectric-horn (built-in) 

Alarm Sound Output:

  85dB (minimum) at 3m 

Temperature Range:

  0 to 40°C 

Humidity Range:

 

15%  to  95%  Relative  Humidity  – 
non condensing 

Interconnect:

 

Hardwire  interconnect  up  to  12 
battery powered alarms. 

A  combination  of  up  to  12  battery 

and Mains powered alarms  maybe  

interconnected.

Fixing:

 

Screw fixings supplied 

Dimensions: 

115mm 

(diameter) 

45mm 

(height)

Weight: 

200 grams

Warranty:

 

5 year (limited) warranty 

Approvals:

 

Certified to AS3786  
VdS approved to 
BS EN14604:2005, CE approved, 
Manufactured  to  ISO  9001:2000 
quality standards. 