High Capacity Helium Compressor
Introduction
Manual Specifications
Brooks Automation
8040600
Revision A
1-9
Figure 1-6: Cooling Water Flow versus Inlet Temperature
(Three Compressor Modules High Voltage Configuration)
General
provides general High Capacity Helium
Compressor operating specifications.
Table 1-3: General High Capacity Helium Compressor Operating Specifications
Specification
Low Voltage
High Voltage
Part Number
8128908G001 - 3 modules
8128904G003 - 2 modules
8128903G003 - 3 modules
8128908G002 - 3 modules
8128904G004 - 2 modules
8128903G004 - 3 modules
Input Power Cable
(
Check local electrical
codes
.)
3 conductor cable with ground
Rated 600 VAC
Check local electrical codes
3 conductor cable with ground
Rated 600 VAC
Check local electrical codes
Helium Static Pressure
325 - 335 psig
(22.4 - 23.1 bars)
325 - 335 psig
(22.4 - 23.1 bars)
Ambient
Operating Temperature
Range
50 - 100º F
(10 - 38º C)
50 - 100º F
(10 - 38º C)
High Capacity (High Voltage) Compressor Cooling Water Flow Rate vs Inlet Temperature
60 Hz Operation, 3 compressor unit
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
50
55
60
65
70
75
80
85
90
Cooling Water Inlet Temperature, degrees F
R
e
c
o
m
m
e
nde
d Minim
u
m
Flow R
a
te
, gpm
342-355 VAC 60 Hz
355-365 VAC 60 Hz
365-375 VAC 60 Hz
375-506 VAC 60 Hz