OWS Standalone Manual
MA380 - Rev. 2.4
6
2
OPERATIONS
2.1 Display Layouts
The OWS main display layout is shown in Figure 2.
PA
PA
Auto
Auto
Fault
Fault
Man
Man
PA Mic
PA Mic
Isolate
Isolate
Power ON
Power ON
Silenced
Silenced
BROOKS
Silence
Buzzer
Silence
Buzzer
Press
To Talk
Press
To Talk
Evac
Evac
OCCUPANT WARNING SYSTEM
Alert
Alert
Figure 2 Main Display Layouts of Brooks Standalone OWS
2.2 Mode of Operation
The OWS has 3 modes of operation as shown in Figure 2: isolate, automatic and manual mode. Only
one of these modes can be selected at any one time. A mode is selected by pressing the mode selection
button on the display and is indicated by a LED next to the button. Pressing the mode selection button
again will de-select the mode and return to the default automatic mode.
2.2.1 Isolate mode
The OWS operates in the isolate mode as follow:
All the outputs are deactivated.
All the alert, evacuation, PA and background music functions are disabled.
When the trigger input becomes active e.g. alarm signal, either the Alert or Evac LED will flash
based on settings i.e. no tone or voice broadcasted to the speakers.
When a wiring fault is detected, the Fault LED illuminates and the fault relay remains in its active
(normal) state
2.2.2 Automatic mode
In auto mode, when the trigger input is activated, the following will occur:
Audio warning signals (tone and voice) will be broadcasted to all the speakers.
Bi-polarity strobe output will be activated.
Either the Alert or the Evac LED will flash based on the setting.
The buzzer will sound.
5
In software version
≥
V1.5, when the system is left in the isolate or manual mode for more than 5 minutes, the OWS generates fault. This
fault remains active until the system manually exits the isolate or manual mode and default back to auto mode. This feature is added to
avoid leaving the system in non-auto mode.
Summary of Contents for BOWS020W
Page 25: ...OWS Standalone Manual MA380 Rev 2 4 24 Figure 13 F647A Iss 8 OWS 60W Interfaced to CIE...
Page 26: ...OWS Standalone Manual MA380 Rev 2 4 25 Figure 14 F647B Iss 8 OWS 60W Standalone...
Page 27: ...OWS Standalone Manual MA380 Rev 2 4 26 Figure 15 F648A Iss 6 OWS 120W Interfaced to CIE...
Page 28: ...OWS Standalone Manual MA380 Rev 2 4 27 Figure 16 F648B Iss 9 OWS 120W Standalone...
Page 29: ...OWS Standalone Manual MA380 Rev 2 4 28 Figure 17 F649A Iss 6 OWS 250W Interfaced to CIE...
Page 30: ...OWS Standalone Manual MA380 Rev 2 4 29 Figure 18 F649B Iss 6 OWS 250W Standalone...
Page 31: ...OWS Standalone Manual MA380 Rev 2 4 30 Figure 19 F649C Iss 7 OWS 500W Interfaced to CIE...